10-74
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Analog input terminals 10 / 11
(analog selectable input 3)
P731
FDS
(G114)
Normalization of "Analog selectable input 3"
This parameter specifies the percentage value which is generated for an
input voltage of 10V (or an input current of 20mA) at the analog input.
The following generally applies:
For voltage input:
P
V
Y
X
731
10
[%]
=
∗
X .. Input voltage in volts
Y .. % value which is generated for input
voltage
X
With current input:
P
mA
Y
X
731
20
[%]
=
∗
X .. Input current in mA
Y .. % value which is generated for input
current X
-1000.0 to 1000.0
[%]
0.1%
Ind: 4
FS=100.0
Type: I2
P052 = 3
P051 = 40
Online
P732
(G114)
Offset for "Analog selectable input 3"
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P733
*
(G114)
Mode of signal injection at "Analog selectable input 3"
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P734
*
(G114)
Source for selection of sign reversal at "Analog selectable input 3"
Selection of binector to control
sign reversal at the analog input
("1" state
= reverse sign)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P735
(G114)
Filtering time for "Analog selectable input 3"
Note: Hardware filtering of approximately 1 ms is applied as standard.
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P736
*
(G114)
Source for enabling of "Analog selectable input 3"
Selection of binector to control
enabling of the analog input
("1" state =
enabled)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
Analog input terminals 103 / 104
(main actual value)
P741
FDS
(G113)
Normalization for "Main actual value”
Rated value of input voltage at nmax (=tachometer voltage at maximum
speed)
This parameter defines the maximum speed when P083=1.
-270.00 to 270.00
[V]
0.01V
Ind: 4
FS=60.00
Type: I2
P052 = 3
P051 = 40
Online
P742
(G113)
Offset for "Main actual value" analog input
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P743
*
(G113)
Mode of signal injection at "Main actual value" analog input
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P744
*
(G113)
Source for selection of sign reversal at "Main actual value" analog
input
Selection of binector to control
sign reversal at the analog input
("1" state
= reverse sign)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P745
(G113)
Filtering time for "Main actual value" analog input
Note: Hardware filtering of approximately 1 ms is applied as standard.
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online