Technical specifications
6.1 Technical specifications
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
Equipment Manual, 08/2020, A5E48753535-AA
41
Article number
6ES7144-5KD50-0BA0
Analog inputs
Number of analog inputs
4
•
For voltage measurement
4
•
For resistance/resistance thermometer
measurement
4
•
For thermocouple measurement
4
permissible input voltage for voltage input
(destruction limit), max.
15 V
Constant measurement current for resistance-
type transmitter, typ.
230 ... 300 µA
Cycle time (all channels), min.
90 ms
Technical unit for temperature measurement
adjustable
Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges (rated values), voltages
•
-80 mV to +80 mV
Yes; 16 bit incl. sign
–
Input resistance (-80 mV to +80 mV)
10 M
Ω
Input ranges (rated values), thermocouples
•
Type B
Yes; 16 bit incl. sign
–
Input resistance (Type B)
10 M
Ω
•
Type C
Yes; 16 bit incl. sign
–
Input resistance (Type C)
10 M
Ω
•
Type E
Yes; 16 bit incl. sign
–
Input resistance (Type E)
10 M
Ω
•
Type J
Yes; 16 bit incl. sign
–
Input resistance (type J)
10 M
Ω
•
Type K
Yes; 16 bit incl. sign
–
Input resistance (Type K)
10 M
Ω
•
Type L
Yes; 16 bit incl. sign
–
Input resistance (Type L)
10 M
Ω
•
Type N
Yes; 16 bit incl. sign
–
Input resistance (Type N)
10 M
Ω
•
Type R
Yes; 16 bit incl. sign
–
Input resistance (Type R)
10 M
Ω
•
Type S
Yes; 16 bit incl. sign
–
Input resistance (Type S)
10 M
Ω
•
Type T
Yes; 16 bit incl. sign
–
Input resistance (Type T)
10 M
Ω
•
Type U
Yes; 16 bit incl. sign
–
Input resistance (Type U)
10 M
Ω
Summary of Contents for 6ES7144-5KD50-0BA0