Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
Equipment Manual, 08/2020, A5E48753535-AA
23
Note
Unused channels
"Deactivate" unused inputs in the parameter assignment to shorten the cycle time of the
module.
A deactivated input always returns the value 7FFF
H
.
Value ranges of the hardware interrupts
The table below shows the permitted value ranges of the hardware interrupts for the
measurement type.
Table 4- 3
Value ranges of the hardware interrupts
Measurement
type
Measuring range
Low limit
High limit
Unit
Voltage
± 80 mV
-94.071
94.068
mV
-32511
32510
Decimal
Resistance
150 ohm
0.01
176.38
Ω
2
32510
Decimal
300 ohm
0.01
352.76
Ω
1
32510
Decimal
Thermal resistance Pt 100 Std.
Pt 1000 Std.
-242.9
999.9
°C
-2429
9999
Decimal
-405.3
1831.9
F
-4053
18319
Decimal
30.3
1273.1
K
303
12731
Decimal
Pt 100 Cl.
Pt 1000 Cl.
-144.99
154.99
°C
-14499
15499
Decimal
-228.99
310.99
F
-22899
31099
Decimal
Ni 100 Std.
Ni 1000 Std.
-104.9
294.9
°C
-1049
2949
Decimal
-156.9
562.9
F
-1569
5629
Decimal
168.3
568.1
K
1683
5681
Decimal
Ni 100 Cl.
Ni 1000 Cl.
-104.99
154.99
°C
-10499
15499
Decimal
-156.99
310.99
F
-15699
31099
Decimal