Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
22
Equipment Manual, 08/2020, A5E48753535-AA
Parameter
Value range
Default
Effective range with config-
uration software e.g. STEP 7
(TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Smoothing
•
None
•
Weak
•
Medium
•
Strong
None
Channel
Channel
Interference fre-
quency suppression
•
60 Hz (16.6 ms)
•
50 Hz (20 ms)
1
•
16.6 Hz (60 ms)
50 Hz (20 ms)
1
Channel
Channel
Diagnostics:
Reference junction
•
Disable
•
Enable
Disable
Channel
Channel
Diagnostics:
Wire break
•
Disable
•
Enable
Disable
Channel
Channel
Diagnostics
Overflow/underflow
diagnostics
•
Disable
•
Enable
Disable
---
Channel
Diagnostics:
Underflow
•
Disable
•
Enable
Disable
Channel
---
Diagnostics:
Overflow
•
Disable
•
Enable
Disable
Channel
---
Conductor re-
sistance [m
Ω
]
2
0 ... 50000 m
Ω
0
Channel
---
Hardware interrupt
high limit 1
•
Disable
•
Enable
Disable
Channel
---
Hardware interrupt
low limit 1
•
Disable
•
Enable
Disable
Channel
---
Hardware interrupt
high limit 2
•
Disable
•
Enable
Disable
Channel
---
Hardware interrupt
low limit 2
•
Disable
•
Enable
Disable
Channel
---
High limit 1
The value range depends on
the measurement type.
The value range (min./max.)
permitted for the measure-
ment type is listed in the
table 4-3
Value ranges of
the hardware interrupts
.
27648
Channel
---
Low limit 1
0
Channel
---
High limit 2
27648
Channel
---
Low limit 2
0
Channel
---
1
Interference frequency suppression: Noise at 400 Hz is automatically included in the filtering at
50 Hz.
2
For 2-wire connection only
Summary of Contents for 6ES7144-5KD50-0BA0
Page 1: ......