Operation
95
SIPART PS2 PA Manual
A5E00127926--05
The display of the positioner shows you the current potentiometer
setting in the top line and ”NOINI” flashes in the second line. You can
move the actuator with the decrement and increment key
. In order
to adapt the positioner to your actuator, you have to change to the
Configuration menu. See also chapter 3.6, page 74 ”Commissioning”.
Manual and automatic mode or output of alarms and position feedback
are possible after successful initialization.
To go to the Configuration menu, press the operation mode key
for
at least 5 seconds. In the Configuration menu you can adapt the
positioner individually to your actuator and start initialization. Only a few
parameters need to be set in the positioner prior to initialization. The
others are defaulted so that they do not normally need to be adjusted.
You can block the Configuration menu against manipulation by an
appropriately parameterized and activated binary input. Which
parameters you need to set and all other parameters are explained in
chapter 4.4, page 97 Parameterization.
The configuration mode can be reported by outputting a
parameterizable fault message, a position feedback or output of limit
values A1 and A2 is not possible in configuration mode.
.
NOTE
If the electric power supply fails during configuration, the positioner
switches back to the first parameter after recovering the power supply,
values which have already been parameterized are retained. When
doing this, please note that the new value will only be saved when
leaving the configuration menu or when another parameter is selected.
Without a power failure you re-enter the configuration menu at the
point you exited it when you call the Configuration menu again.
P--manual mode
(ex--factory state)
Configuration and
initialization
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...
Page 132: ...Operation 130 SIPART PS2 PA Manual A5E00127926 05 ...
Page 160: ...Functions operation via PROFIBUS PA 158 SIPART PS2 PA Manual A5E00127926 05 ...
Page 163: ...Technical data 161 SIPART PS2 PA Manual A5E00127926 05 Technical data see following pages 7 ...
Page 177: ......