Functions/operation via PROFIBUS PA
148
SIPART PS2 PA Manual
A5E00127926--05
Hex
Action
Cause
PDM display
Accompanying
status code
Dez
1F
31
READBACK, POS_D
bad,
out of service,
value
constant
Function block has been
disabled by command. Device
will move to safety position
For normal operation reinstate
target mode ”AUTO”
47
71
READBACK, POS_D
uncertain,
last useful
value, value
constant
Connection is disconnected or
the SETPOINT status is not
”Good”. Positioner will move
to safety position, the para--
meterized safety setting is set
to ”retain last valid value”
Check the connection and
make sure that the
SETPOINT (SP) is
accompanied by a status of
80 hex., 128 decimal (Good)
48
75
READBACK, POS_D
uncertain,
substituted
value, value
constant
Connection is disconnected or
the SETPOINT status is not
”Good”. Positioner will move
to safety position, the parame-
terized safety setting is set to
”issue default value”
Check the connection and
make sure that the
SETPOINT (SP) is
accompanied by a status of
80 hex., 128 decimal (Good)
4F
75
READBACK, POS_D
uncertain,
iinitial value,
value
constant
After powering up an initial
value is entered ion the device
memory
Discard the value in the
application program
53
83
READBACK, POS_D
uncertain,
value
uncertain
Device will be controlled
locally
80
128
SETPOINT (SP),
READBACK,
POS_D
Good
Normal operation
------
84
132
READBACK, POS_D
Good, update
event
A parameter relevant to the
device has been changed.
This display will expire after
10 sec.
8D
141
READBACK,
Good, alarm
value fallen
below
Out of tolerance below lower
parameterized alarm limit.
Alarm output A1 or A2 will be
activated
------
8E
142
READBACK, POS_D
Good, alarm
value
exceeded
Out of tolerance above upper
parameterized alarm
limit.Alarm output A1 or A2 will
be activated
------
A3
163
SETPOINT (SP)
Good,
Go to
Fail--Safe
Command to take up the
safety position
For normal operation the
status 80 hex., 128 decimal
(Good) must be restored
A4
164
READBACK, POS_D
Good,
maintenance
requested
The travel integral limit value
has been exceeded by the ab-
solute travel integral
Perform maintenance and
reset the reports using
SIMATIC PDM
Table 9
Status codes
5.3.2.2
Diagnostics
As well as status information the device can also report active
information regarding the device condition. Diagnostics are important
information which can be used in an automation system purposes of
determining remedial action.
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...
Page 132: ...Operation 130 SIPART PS2 PA Manual A5E00127926 05 ...
Page 160: ...Functions operation via PROFIBUS PA 158 SIPART PS2 PA Manual A5E00127926 05 ...
Page 163: ...Technical data 161 SIPART PS2 PA Manual A5E00127926 05 Technical data see following pages 7 ...
Page 177: ......