Functions/operation via PROFIBUS PA
133
SIPART PS2 PA Manual
A5E00127926--05
To see the values displayed, open the ”Device” menu and open the
”Read maintenance information” submenu. Because there is so much
information, these are divided amongst several registers:
S
Maintenance information 1 and 2
here the initialization values such as zero point P0, end value P100,
positioning times etc. are displayed.
S
Maintenance data
gives information regarding number of strokes, changes of direction,
fault messages etc. In addition limit values can be entered and
transmitted to the device.
S
Operating temperature
displays the minimum, current and maximum temperature.
S
Service times
displays the total service time and the service times at different
temperature bands.
S
Static data revision number
This parameter shows the revision issue of data associated with the
respective PROFIBUS block. After each parameter change the
revision issue in the respective PROFIBUS block is incremented.
5.2.1.5
Set maintenance information
This allows maintenance information to be saved and reset.
Open the ”Device” menu and open the ”Set maintenance information”
submenu. The following registers are displayed:
S
Save / reset maintenance information
and
S
Reset counter
To save the current initialization values, enter a valid date into the field
”Date of SIPART maintenance” and then press the ”Save maintenance
information” key. This leads to a double column display of the
maintenance information in the ”Read maintenance information” menu
(see above). If the positioner is subsequently re--initialized, the current
values will be determined and these can be compared with the
previously saved values.
By pressing the ”Reset maintenance information” key, the ”Values at
the last maintenance’ will be reset (cleared down). Resetting the
maintenance parameters is done by setting the ’Date of last
maintenance’ to a nonsensical value (1.1.00). This deceives the PDM
into believing that there is no ’last maintenance’ data.
TIP
: if a valid data is then re--input, the old values will once again be
displayed.
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...