Operation
114
SIPART PS2 PA Manual
A5E00127926--05
No.
Rest
poss.
Unit
Displayable
values
Meaning
Abbrevia--
tion
28
T7
Number of operating hours in
T
emperature range
7
0 to 4.29E9
Hours
29
T8
Number of operating hours in
T
emperature range
8
0 to 4.29E9
Hours
30
T9
Number of operating hours in
T
emperature range
9
0 to 4.29E9
Hours
31
VENT1
Number of cycles pre--control
valve 1
0 to 4.29E9
--
32
VENT2
Number of cycles pre--control
valve 2
0 to 4.29E9
--
33
STORE
Store current values as ”last maintenance”
(press increment key for 5 s) (
Store
)
--
--
34
PRUP
Prediction up
1 to 40
--
35
PRDP
Prediction down
1 to 40
--
36
WT00
Number of operating hours in distance class WT00
0 to 4.29E9
Hours
x
37
WT05
Number of operating hours in distance class WT05
0 to 4.29E9
Hours
x
38
WT10
Number of operating hours in distance class WT10
0 to 4.29E9
Hours
x
39
WT30
Number of operating hours in distance class WT30
0 to 4.29E9
Hours
x
40
WT50
Number of operating hours in distance class WT50
0 to 4.29E9
Hours
x
41
WT70
Number of operating hours in distance class WT70
0 to 4.29E9
Hours
x
42
WT90
Number of operating hours in distance class WT90
0 to 4.29E9
Hours
x
43
WT95
Number of operating hours in distance class WT95
0 to 4.29E9
Hours
x
Table 1
Overview diagnostic values
4.5.2 Meaning of the diagnostic values
Number of strokes (total valve travel)
The actuator movements during operation are totaled and can be read
here as number of strokes. Unit: 100% stokes, i.e. the distance
between 0 to 100 % and backwards. The value is written every 15
minutes in a non--volatile memory. It can be reset to zero with the
increment key
.
Number of direction changes
Every change in direction leaving the dead zone is noted in the
controller and added to the number of changes of direction.
The value is written every quarter of an hour in a non--volatile memory.
It can be reset to zero with the increment key
.
Fault counter
Every fault is noted in the controller and added to the number of fault
messages. The counter can be reset to zero with the increment
key--
.
1 STRKS
2 CHDIR
3 CNT
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...
Page 132: ...Operation 130 SIPART PS2 PA Manual A5E00127926 05 ...
Page 160: ...Functions operation via PROFIBUS PA 158 SIPART PS2 PA Manual A5E00127926 05 ...
Page 163: ...Technical data 161 SIPART PS2 PA Manual A5E00127926 05 Technical data see following pages 7 ...
Page 177: ......