Functions/operation via PROFIBUS PA
142
SIPART PS2 PA Manual
A5E00127926--05
The checkback is displayed bit--coded in 3 bytes:
Bit
Meaning for ”1”
Notes
0
0
Device in failsafe position
Position determined by parameter 46 (FSTY)
1
Request for local operation
Reports that a key has been pressed
2
Device is operated locally
Device locally parameterized (e.g. 1 YFCT) or is not
initialized
3
Emergency operation active
Device is in manual mode (display : Man or P)
4
Deviation of the motion direction
Not required for the positioner
5
Stop reached (valve not completely open)
Not required for the positioner
6
Stop reached (valve not completely closed)
Not required for the positioner
7
Operating timeout
Device cannot be adjusted (monitoring time and mo-
nitoring threshold exceeded, parameters 43 TIM and
44 LIM) due to lack of compressed air.
1
0
Valve is opened
Setting command ”Supply air to actuator” sent
1
Valve is closed
Setting command ”Exhaust air from actuator” sent
2
Parameters have been changed
Set a short time after quitting ”Configuration mode”, if
one or more parameters have been changed
3
Simulation operation
Simulation mode has been approved. Master class 2
can overwrite actual data values, e.g. for purposes of
testing the response at the limits of the control
system
4
Is not preset in Profile 3
5
Fault in the contrl
Not required for the positioner
6
Control inactive
Not required for the positioner
7
Self test active
Not required for the positioner
2
0
Path integral exceededn
Will be set if the limit value set for travel integral is
exceeded.
1
Additional input active
Binary input 1 is activated
2
Additional input active
Binary input 2 is activated
In remote cascade mode (actual mode = remote cascade), the remote
cascade input is used as the setpoint. Remote cascade input consists
of a floating-point value (4 bytes) and status (1 bytes).
This output provides the current setpoint in AUTO mode and remote
cascade. The status is used especially for the transition from AUTO to
remote cascade.
In conjunction with the parameter input variable (primary value scale)
you cannot only set the setpoints to the positioner as a percentage of
the valve position but also in physical quantities such as cubic meters
per day or liters per minute. It is also possible to adapt the readbacks
to this scaling.
Checkback
Remote cascade
input
Remote cascade
output
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...
Page 132: ...Operation 130 SIPART PS2 PA Manual A5E00127926 05 ...
Page 160: ...Functions operation via PROFIBUS PA 158 SIPART PS2 PA Manual A5E00127926 05 ...
Page 163: ...Technical data 161 SIPART PS2 PA Manual A5E00127926 05 Technical data see following pages 7 ...
Page 177: ......