Operation
101
SIPART PS2 PA Manual
A5E00127926--05
.
NOTE
After ”LWAY, ncSt, --ncSt or ncSL, ncSLL” have been adjusted, both
the following parameters ”2. YAGL” and ”3. YWAY” will not be
displayed.
Rated angle of rotation of the feedback shaft
In part--turn actuators, an angle of 90
°
is preset automatically by
1.YFCT = turn (see above). In linear actuators (1.YFCT = WAY) a
value of 33
°
or 90
°
can be selected depending on the stroke range:
S
33
°
for strokes
≤
20 mm
S
90
°
for strokes > 20 mm
When using the lever up to 35 mm, both angles of rotation (33
°
and
90
°
) are possible.
The long lever (> 35 mm stroke) is only designed for an angle of
rotation setting of 90
°
. It is not part of the mounting kit set
6DR4004--8V but must be ordered separately under order number
6DR4004--8L.
.
NOTE
The setting of the transmission ratio selector on the positioner (see
figure 8, page 25 and figure 9, page 26)
must
correspond to the angle
value selected under ”2.YAGL”.
Lever arm transmission
.
NOTE
The use of this parameter is optional. You only need to set this
parameter if you want to have the way in mm displayed at the end of
the initialization.
Selection of the lever arm range: serves to display the real stroke after
initialization.
This parameter is only relevant for linear actuator. If the parameter
value ”oFF” is selected here, the real stroke is not displayed after
initialization.
.
NOTE
The specification ”YWAY” must match the mechanical lever arm trans-
mission. The carrier must be set to the value of the actuator stroke, if
this is not scaled to the next highest scaled value.
2.YAGL
3.YWAY
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...
Page 132: ...Operation 130 SIPART PS2 PA Manual A5E00127926 05 ...
Page 160: ...Functions operation via PROFIBUS PA 158 SIPART PS2 PA Manual A5E00127926 05 ...
Page 163: ...Technical data 161 SIPART PS2 PA Manual A5E00127926 05 Technical data see following pages 7 ...
Page 177: ......