Technical data
163
SIPART PS2 PA Manual
A5E00127926--05
■
Technical specifications
SIPART PS2 PA
Basic device
without Ex protection
Basic device
with EEx-d protection
(flameproof casing)
Basic device
with EEx ia/ib protection
Basic device
with EEx n protection
Explosion protection to
EN 50014, EN 50020 and EN 50021
Without
EEx d
II 2 G EEx d II C T4/T5/T6
EEx ia/ib
II 2 G EEx ia/ib II C T6
EEx n
II 3 G EEx nA L [L] II C T6
Mounting location
Zone 1 or zone 2
Zone 1
Zone 2
Permissible ambient temperature for
operation
At
≤
-10 °C (+14 °F) the display refresh
rate of the LCD is limited.
(for basic devices with Ex protection
the following applies: Only T4 is per-
missible when using I
y
module.)
-30 ... +80 °C
(-22 ... +176 °F)
T4: -30 ... +80 °C (-22 ... +176 °F)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
Electrical data
Input
Power supply (terminals 6/7)
Bus-supplied
Bus voltage
9 ... 32 V
9 ... 32 V
9 ... 24 V
9 ... 32 V
• Bus connection with FISCO supply
unit,
ia or ib group IIC or IIB
–
- Max. supply voltage U
o
–
–
17.5 V
–
- Max. short-circuit current I
o
–
–
380 mA
–
- Max. power P
o
–
5.32 W
–
• Bus connection with barrier,
ia or ib group IIC or IIB
–
- Max. supply voltage (U
o
)
–
–
24 V
–
- Max. short-circuit current (I
o
)
–
–
250 mA
–
- Max. power P
o
–
–
1.2 W
–
Current consumption
10.5 mA
±
10%
10.5 mA
±
10%
10.5 mA
±
10%
10.5 mA
±
10%
Fault current
0 mA
0 mA
0 mA
0 mA
Effective internal inductance
–
–
Li
≤
8 µH
–
Effective internal capacitance
–
–
Negligible
–
Connection
–
–
Certified intrinsically safe
circuit
–
Safety shutdown can be activated with
coding bridge (terminals 81/82; elec-
trically isolated from the basic device)
• Input resistance
> 20 k
Ω
> 20 k
Ω
> 20 k
Ω
> 20 k
Ω
• Signal status "0" (shutdown active)
0 ... 4.5 V or unused
0 ... 4.5 V or unused
0 ... 4.5 V or unused
0 ... 4.5 V or unused
• Signal status "1" (shutdown not ac-
tive)
13 ... 30 V
13 ... 30 V
13 ... 30 V
13 ... 30 V
• Effective Internal capacitance C
i
–
–
Negligible
–
• Effective internal inductance L
i
–
–
Negligible
–
• For connection to power supply with –
–
Intrinsically safe
–
- Max. supply voltage U
i
–
–
< 30 V
< 30 V
- Max. short-circuit current I
i
–
–
<100 mA
<100 mA
- Maximum power P
i
–
–
< 1 W
–
Electrical isolation
Between basic device
and the input for safety
shutdown, as well as the
outputs of the option
modules
Between basic device
and the input for safety
shutdown, as well as the
outputs of the option
modules
The basic device and the
input to the safety shut-
down, as well as the out-
puts of the option
modules, are individual,
intrinsically-safe circuits
Between basic device
and the input for safety
shutdown, as well as the
outputs of the option
modules
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...
Page 132: ...Operation 130 SIPART PS2 PA Manual A5E00127926 05 ...
Page 160: ...Functions operation via PROFIBUS PA 158 SIPART PS2 PA Manual A5E00127926 05 ...
Page 163: ...Technical data 161 SIPART PS2 PA Manual A5E00127926 05 Technical data see following pages 7 ...
Page 177: ......