Operation
122
SIPART PS2 PA Manual
A5E00127926--05
4.6 Meanings of other display texts
Notes on the tables:
nn
stands for variable numerical values
Fault symbol
/
(slash): the texts to the left and right of the slash
flash alternately
Reports before initializing (first commissioning):
Upper lin
e
Lower lin
e
Meaning/Cause
Actions
CPU
START
x
x
Report after connecting the electrical
auxiliary power
S
· Wait
P
nnn.n
x
Potentiometer voltage for non--
initialized positioner (P manual
mode) (Setting actual value in % of
measurement range)
S
Check using the ”+” and ”--” keys
whether the overall actuator travel
can be traversed without ever ”
P------
”
being displayed
S
Perform initialization
P------
x
Measurement range exceeded,
potentiometer is in the inactive zone,
transmission ratio selector or
effective lever arm are not matched
to the actuator travel
S
Set transmission ratio selector to 90
degrees, in particular for part--turn
actuators
S
Match effective arm length for thrust
drives to measurement range
NOINI
x
Positioner not initialized
S
Start initialization
Messages during initialization:
Upper lin
e
Lower lin
e
Meaning/Cause
Actions
P----
x
See above
See above
RUN 1
x
Initialization started, part 1 active
(direction of control action being
determined)
S
Wait
RUN 2
x
Initialization part 2 active
(actuator travel check and
determination of the end stops)
S
Wait
RUN 3
x
Initialization part 3 active
(determination and display of
positioning times)
S
Wait
RUN 4
x
Initialization part 4 active
(determination the minimum
positioning increment length)
S
Wait
RUN 5
x
Initialization part 5 active
(optimization of the behavior on
transients)
S
Wait until ”FINSH” is displayed
(initialization completed successfully)
S
Press ”operating mode” key briefly to
acknowledge or longer to quit
configuration mode
YEND1
x
only during manual initialization
first end position can be moved to
S
Move to first end position using the
”+” or ”--” key
S
Press ”operating mode” key to
acknowledge
Summary of Contents for 6DR55 Series
Page 2: ......
Page 8: ...6 SIPART PS2 PA Manual A5E00127926 05 ...
Page 24: ...Introduction 22 SIPART PS2 PA Manual A5E00127926 05 ...
Page 46: ...Design and method of operation 44 SIPART PS2 PA Manual A5E00127926 05 ...
Page 92: ...Preparing for operation 90 SIPART PS2 PA Manual A5E00127926 05 ...
Page 132: ...Operation 130 SIPART PS2 PA Manual A5E00127926 05 ...
Page 160: ...Functions operation via PROFIBUS PA 158 SIPART PS2 PA Manual A5E00127926 05 ...
Page 163: ...Technical data 161 SIPART PS2 PA Manual A5E00127926 05 Technical data see following pages 7 ...
Page 177: ......