Description
24
9229 9860 176 0E
2013-08-22
Motor M1
*)
The operator's supply voltage may deviate from the rated supply voltage of the
vacuum circuit-breaker by -15 % to +10 %.
**) Built-in automatic circuit-breaker with C characteristic.
Fig. 28
Recommendation for motor protection device
Contactor relay K1
After the supply voltage is applied and if the closing
spring is discharged, the motor starts immediately and
is automatically deactivated internally after charging has
taken place.
Power consumption, maximum:
•
in the event of direct voltage approx. 750 W
•
in the event of alternating voltage 1400 W.
In the short charging time, the motor temporarily oper-
ates in the overload range. See Fig. 28 for the rated cur-
rent for the required motor short-circuit protection.
Note: The motor protection devices are not included in
the delivery of the vacuum circuit-breaker and must be
ordered separately.
Fig. 27
Motor (50.4)
Rated supply voltage U*
)
V
DC
24
DC
48
DC
60
DC
110
AC 50/60 Hz
110
DC
220
AC 50/60 Hz
230
Recommended rated current of the protective
device I**
)
A
16
10
6
4
6
2
3
If simultaneous CLOSE and OPEN commands are con-
tinuously applied to the vacuum circuit-breaker, it returns
to the open position after being closed.
Via the function of the contactor relay K1, the vacuum
circuit-breaker pauses there until the CLOSE command
is given again.
This prevents continuous closing and opening (pump-
ing).
Fig. 29
Contactor relay (69.)
Summary of Contents for 3AH3
Page 4: ...4 9229 9860 176 0E 2013 08 22 Blank page ...
Page 16: ...Transport storage and packing 16 9229 9860 176 0E 2013 08 22 Blank page ...
Page 52: ...Operation 52 9229 9860 176 0E 2013 08 22 Blank page ...
Page 58: ...Maintenance 58 9229 9860 176 0E 2013 08 22 Blank page ...
Page 60: ...Index of keywords 60 9229 9860 176 0E 2013 08 22 Blank page ...
Page 62: ...62 9229 9860 176 0E 2013 08 22 Blank page ...
Page 63: ...9229 9860 176 0E 63 2013 08 22 Blank page Siemens Parts ...