Description
26
9229 9860 176 0E
2013-08-22
Auxiliary switch S1
Breaking capacity
Fig. 33
Breaking capacity of the auxiliary switch 3SV92
Two versions of the auxiliary switch S1 are available for
delivery: with 6 or 12 NO/NC contacts each.
Rated insulation voltage:
250 V AC/DC
Insulation group:
C as per VDE 0110
Continuous current:
10 A
Closing capacity:
50 A
Fig. 32
Auxiliary switch (68.)
AC 40 to 60 Hz
DC
Operating voltage
Operating current
Operating voltage
Operating current
U (V)
I (A)
U (V)
I (A)
Ohmic load
Inductive load
(T = 20 ms)
Up to 230
10
24
10
10
48
10
9
60
9
7
110
5
4
220
2.5
2
Summary of Contents for 3AH3
Page 4: ...4 9229 9860 176 0E 2013 08 22 Blank page ...
Page 16: ...Transport storage and packing 16 9229 9860 176 0E 2013 08 22 Blank page ...
Page 52: ...Operation 52 9229 9860 176 0E 2013 08 22 Blank page ...
Page 58: ...Maintenance 58 9229 9860 176 0E 2013 08 22 Blank page ...
Page 60: ...Index of keywords 60 9229 9860 176 0E 2013 08 22 Blank page ...
Page 62: ...62 9229 9860 176 0E 2013 08 22 Blank page ...
Page 63: ...9229 9860 176 0E 63 2013 08 22 Blank page Siemens Parts ...