Mounting
48
9229 9860 176 0E
2013-08-22
Corresponding to the rated current strength, use M12 screws and nuts – strength
class 8.8 – for connection of the busbars and use the appropriate spring elements
and washers.
When tightening the screws, hold the nuts against tightening torque of 70 Nm with
a suitable screwdriver or socket wrench.
Screw-in depths in the upper and lower terminals
See dimension drawings.
Note
For vacuum circuit-breakers with connecting bars, it is recommended to use the
stainless steel screws or non-magnetisable screws included in the accessory
pack.
Fig. 68
Installing busbars flat
Fig. 69
Installing busbars flat
Summary of Contents for 3AH3
Page 4: ...4 9229 9860 176 0E 2013 08 22 Blank page ...
Page 16: ...Transport storage and packing 16 9229 9860 176 0E 2013 08 22 Blank page ...
Page 52: ...Operation 52 9229 9860 176 0E 2013 08 22 Blank page ...
Page 58: ...Maintenance 58 9229 9860 176 0E 2013 08 22 Blank page ...
Page 60: ...Index of keywords 60 9229 9860 176 0E 2013 08 22 Blank page ...
Page 62: ...62 9229 9860 176 0E 2013 08 22 Blank page ...
Page 63: ...9229 9860 176 0E 63 2013 08 22 Blank page Siemens Parts ...