Description
36
9229 9860 176 0E
2013-08-22
Ambient conditions
Installation altitudes
Insulating capacity
The insulating capacity of insulation in air decreases with rising altitude due to the
lower air density. In conformity with IEC 62271-102, the rated lightning impulse volt-
age values given in Fig. 47 are valid up to an installation altitude of 1,000 m above
sea level.
At altitudes of 1,000 m and higher, the insulation level must be corrected as shown
in Fig. 49:
3AH3 vacuum circuit-breakers are suitable for use in the
following climate classes in accordance with IEC 60721,
Part 3-3:
Class
•
Climatic ambient conditions:
3K4
1)
,
3K6
2)
,
3Z2,
3Z5
•
Biological ambient conditions:
3B1
•
Mechanical ambient conditions:
3M2
•
Chemically active substances:
3C2
3)
•
Mechanically active substances:
3S2
4)
1)
Peak value of the 24-hour means: +35 °C
2)
Without ice formation and wind-driven precipitation
3)
Without occurrence of salt fog and simultaneous condensation
4)
Restriction: clean insulating parts
5)
Average value, measured over 24 hours
6)
Average value, measured over 1 month
Fig. 48
Ambient conditions
U
U
0
K
a
U
Rated withstand voltage U under standard reference
atmosphere
U
0
Required rated withstand voltage for the installation
location
K
a
Altitude correction factor
K
a
= e
m
(H – 1000)/8150
Calculating the altitude correction factor
K
a
:
H
=
Installation altitude in metres
m = 1 for AC voltage, lightning impulse voltage (between
phases, phase-to-earth, applied longitudinally)
Example
For a required rated withstand voltage of 75 kV at an alti-
tude of 2,500 m, an insulation level of at least 90 kV
under standard reference atmosphere conditions is
required:
90 kV
75 kV
e
1
(2500 – 1000)/8150
75 kV
1.2
Fig. 49
Altitude correction factor
K
a
Summary of Contents for 3AH3
Page 4: ...4 9229 9860 176 0E 2013 08 22 Blank page ...
Page 16: ...Transport storage and packing 16 9229 9860 176 0E 2013 08 22 Blank page ...
Page 52: ...Operation 52 9229 9860 176 0E 2013 08 22 Blank page ...
Page 58: ...Maintenance 58 9229 9860 176 0E 2013 08 22 Blank page ...
Page 60: ...Index of keywords 60 9229 9860 176 0E 2013 08 22 Blank page ...
Page 62: ...62 9229 9860 176 0E 2013 08 22 Blank page ...
Page 63: ...9229 9860 176 0E 63 2013 08 22 Blank page Siemens Parts ...