06.2006
Connecting-up
Siemens AG
6SE7087-6KP50
SIMOVERT MASTERDRIVES
Operating Instructions
7-17
The checkback contacts of the safety relay are capable of at least
100,000 switching cycles at the specified load (30 V DC / 1 A). The
mechanical service life is about 10
6
switching cycles. The safety relay is
an important component in ensuring reliability and availability of the
machine. For this reason, the pcb with the safety relay must be
replaced in the case of malfunction. In this case, the unit must be
returned for repair or replaced. Function checks must be carried out at
regular intervals, which must be defined in compliance with Employer's
Liability Insurance Regulation BGV A1 §39, para. 3. Accordingly,
function checks must be performed as required by the relevant service
conditions, but at least once a year and additionally after initial
commissioning and any modification and/or maintenance work.
P24
1
2
3
4
M
-Cu control
board
PV
SIMOVERT
MASTERDRIVES
Option K80
X101
X533
U1 V1 W1
U2 V2 W2
X
Y
M
3
-K1
K1
-Q1
Main switch
Mains
closed
open
A1
Y10
Y21 Y22
Y11 Y12
13
14
3TK2828
24
23
31
47
57
32
48
58
Y33 Y34
PE
A2
A1
Y10 Y11 Y12
Y21 Y22
13
14
3TK2828
24
23
31
47
57
32
48
58
Y33 Y34
PE
A2
OFF3
n = 0
-K2
-Y1
K2
-S1
K1
K2
P24
M
X: Binary input, connect to OFF3
e. g. X101.8 --> P558 = 21
Y: Binary output, connect to "Comparison value
reached"
e. g. X101.6 --> P654 = 120; P796 = 0 (comparison value)
Emerg.
stop
S2
Request protective
device enable
S3
Reset
OFF1
Fig. 7-6
Sample application of "safe stop" function with contactor safety
combination for monitoring a moving protective device in Safety Category
3 to EN 954-1
Summary of Contents for 12-0TP50
Page 3: ......
Page 11: ......
Page 13: ......
Page 49: ......
Page 79: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 30 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 81: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 32 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 83: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 34 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 85: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 36 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 87: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 38 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 99: ......
Page 103: ......
Page 153: ......
Page 161: ......
Page 163: ......
Page 199: ......
Page 249: ......
Page 253: ......
Page 301: ......
Page 304: ......