Faults and Alarms
06.2006
6SE7087-6KP50 Siemens
AG
12-16
Operating Instructions
SIMOVERT MASTERDRIVES
Number / Alarm
Cause
Counter-measure
A053
Peer Lng f.
not Compact PLUS
In a peer-to-peer connection, the pcD length of
transmitter and receiver do not match.
Adjust the word length for transmitter and
receiver
P703 SCom/SCB PcD #
A057
TB Param
not Compact PLUS
Occurs when a TB is logged on and present,
but parameter tasks from the PMU, SCom1 or
SCom2 have not been answered by the TB
within 6 seconds.
Replace TB configuration (software)
A061
Alarm 1
Function blocks
An active signal is present at binector U065
(1).
Check cause of alarm (see FD 710)
A062
Alarm 2
Function blocks
An active signal is present at binector U066
(1).
Check cause of alarm (see FD 710)
A063
Alarm 3
Function blocks
An active signal is present at binector U067
(1).
Check cause of alarm (see FD 710)
A064
Alarm 4
Function blocks
An active signal is present at binector U068
(1).
Check cause of alarm (see FD 710)
A072
Frict Char Init
Automatic initiation of the friction characteristic
has been selected, but the drive has not yet
been switched on.
Note: If the ON command is not given within
30 seconds, the automatic initiation of the
friction characteristic is stopped with fault
F099.
Energize drive.
(Drive status "Operation" 014)
A073
Interr InitFric
Automatic initiation of the friction characteristic
has been interrupted (OFF command or fault).
Note:
If the drive is not switched on again within 5
minutes, the automatic initiation of the friction
characteristic is stopped (F099).
Rectifiy any causes of the fault.
Re-energize the drive.
A074
Incompl FricChar
Incomplete initiation of friction characteristic.
As there is a lack of enables or due to
limitations, complete initiation of the friction
characteristic is not possible in both directions.
Grant enable for both directions of rotation.
Set the speed limitations for both directions
such that all characteristic points can be
approached.
A075
Ls,Rr Dev.
The measured values of the leakage
measurement or of rotor resistance deviate
significantly.
If individual measured values significantly
deviate from the average values, they are
automatically disregarded in the calculation
(for RI) or the value of the automatic
parameterization remains (for Ls).
It is only necessary to check the results for
their plausibility in the case of drives with high
requirements on torque or speed accuracy.
A078
Stands. Meas
The standstill measurement is executed when
the converter is powered up. The motor can
align itself several times in a certain direction
with this measurement.
If the standstill measurement can be executed
without any danger:
- Power up the converter.
A081
CB alarm
The following description refers to the 1st
CBP. For other CBs or the TB see operating
instructions for CB board.
The ID byte combinations which are being
sent from the DP master in the configuration
telegram are not in conformance with the
permissible ID byte combinations. (See also
Compendium, Chapter 8, Table 8.2-12).
Consequence:
No connection is made with the PROFIBUS
master.
New configuration necessary
Summary of Contents for 12-0TP50
Page 3: ......
Page 11: ......
Page 13: ......
Page 49: ......
Page 79: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 30 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 81: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 32 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 83: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 34 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 85: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 36 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 87: ...Parametrierung 06 2006 6SE7087 6KP50 Siemens AG 8 38 Betriebsanleitung SIMOVERT MASTERDRIVES ...
Page 99: ......
Page 103: ......
Page 153: ......
Page 161: ......
Page 163: ......
Page 199: ......
Page 249: ......
Page 253: ......
Page 301: ......
Page 304: ......