ELECTRICAL INSTALLATION
5
41
8027439/V1-0/2022-02|SICK
Subject to change without notice
A D D E N D U M T O O P E R A T I N G I N S T R U C T I O N S | Track and trace cabinet TTC100-2
5.2.4
Terminal blocks
Terminal block Function
Cable cross-section
Rigid cable
Flexible cable
-XD100
Mains voltage IN
0.08 ... 6 mm
2
0.08 ... 4 mm
2
-XD101
Ground terminal
Max. 4 mm
2
Max. 2.5 mm
2
-XD113
Terminal for left fan
Max. 1.5 mm
2
Max. 1.5 mm
2
-XD114
Terminal for right fan
Max. 1.5 mm
2
Max. 1.5 mm
2
-XD120
24 V supply voltage to the
ICR cameras
0.08 ... 2.5 mm
2
0.08 ... 2.5 mm
2
-FC1, -FC2, -FC3 24 V supply voltage to the
internal components and
external sensors
0.2 ... 1.5 mm
2
0.2 ... 1.5 mm
2
X1 ... X8
X9 ... X14
Connections on the controller 0.2 ... 1.5 mm
2
0.2 ... 1.5 mm
2
Tab. 7: Wire cross-sections for the terminal blocks in the cabinet
Fig. 25: Connecting wires to the terminal blocks
▸
Remove approx. 10 mm of the insulation from each of the wires.
▸
Use wire sleeves.
NOTE!
Do not solder the wire ends.
▸
Connect the wires to the terminal block as shown. Using a small screwdriver, push the
clamping mechanism downwards.
▸
Insert the wire ends.
NOTE!
Make sure that no wires are sticking out.
▸
Release the clamping mechanism
▸
Check the wires are seated securely.
Wire cross-sections
Connecting the
wire ends