NOTE
•
The information in square brackets reflects the names used in the CDS and in the
Flexi Soft Designer.
•
If the devices are operated in the compatibility mode, then restricted EFI status
information and control commands are available.
Status information
Table 43: Status information of the S3000 (data from the S3000)
Status information
Meaning/effect
•
Logical 1, if the internal OSSDs of the S3000 are in
the ON state (green)
•
Logical 0, if the OSSDs of the S3000 are in the OFF
state (red)
Warning field bit [WF LED]
•
Logical 1, if warning field 1 and warning field 2 of
the S3000 are clear or not used
Contamination [Weak]
•
Logical 1, if the front screen is contaminated
Reset required [Res. Req]
•
Logical 1, if reset required
Reset button pressed [Res. Pressed]
•
Logical 1, if the reset button is pressed on the
S3000
I/O error [I/O Error]
•
Logical 0, if there is no error on the S3000
•
Logical 1, if there is an error on the S3000
•
Logical 1, if the connection of control input A1 is
HIGH
1)
•
Logical 1, if the connection of control input A2 is
HIGH
1)
•
Logical 1, if the connection of control input B1 is
HIGH
1)
•
Logical 1, if the connection of control input B2 is
HIGH
1)
•
Logical 1, if the connection of control input C1 is
HIGH
1)
•
Logical 1, if the connection of control input C2 is
HIGH
1)
•
Logical 1, if the connection of control input D1 is
HIGH
1)
•
Logical 1, if the connection of control input D2 is
HIGH
1)
Allocated protective field clear [PF]
•
In dual field mode, in dual protective field mode
and in triple field mode: Logical 1, if the active allo‐
cated protective field is clear
Allocated warning field clear [WF]
or
Allocated protective field 2 clear [PF2]
•
In dual field mode: Logical 1, if the active allocated
warning field is clear
•
In dual protective field mode: Logical 1, if the active
allocated protective field 2 is clear
•
In triple field mode: Logical 1, if the active allo‐
cated warning field is clear
Simultaneous protective field clear
[Sim. SF]
•
In dual field mode and in dual protective field
mode: Logical 1, if the simultaneously monitored
protective field is clear
•
In triple field mode: no function
TECHNICAL DATA
12
8009942/ZA18/2019-11-14 | SICK
O P E R A T I N G I N S T R U C T I O N S | S3000
151
Subject to change without notice