Angular resolution
Standard
Advanced
Professional
Expert
Remote
Configured angular
resolution 0.5°
1
4
8
21
21
Configured angular
resolution 0.25°
1
4
8
10
10
7.12.1
Configuring the protective field and warning field
The field set, which comprises a protective field
1
and two warning fields
2
is config‐
ured using the CDS. This involves configuring the shape and size of the protective field
and warning field. Any field shape can be created.
The area to be monitored is scanned radially by the device. The device cannot see
through objects, however. The surface behind objects which are located in the area to
be monitored (support columns, separator grids, etc.) can therefore not be monitored.
Figure 74: Creating a field set in the CDS
Protective fields and warning fields can cover an angle of up to 190° and have different
radial scanning ranges depending on the sensor head and the resolution configured.
WARNING
Persons or parts of the body to be protected may not be recognized or not recognized in
time in case of non-observance.
Before commissioning the machine or vehicle, check the configuration of the protective
fields,
see "Checklist for initial commissioning and
.
b
Check the configured protective fields.
NOTE
3
or the warning fields
2
extend all the way to a wall or another
object (pillar, neighboring machine, shelf), there should be a distance of 100 mm
between the protective field or warning field and the object to prevent false triggering
1
.