Operating instructions
Chapter
5
ICR 84x Image Code Reader
Electrical installation
8 010 961/0000/10-05-2005
©
SICK AG · Division Auto Ident · Germany · All rights reserved
5-13
5.5.8
Connecting the “Sensor 1“ switching input
If a reading procedure is to be triggered on the ICR by an external sensor, the reading pulse
sensor must be connected to the “Sensor 1“ switching input. The trigger type is selected in
the default setting of the ICR.
shows the connections for the “Sensor 1“ switching
input.
contains the characteristic data for this input.
¾
Connect the reading pulse sensor as shown in
Tip
You can change the switching mode (polarity, debouncing time, start/stop delay and
response for first pulse after power-up) of the “Sensor 1“ switching input on the D
EVICE
C
ONFIGURATION
tab in the CLV Setup program.
¾
Edit S
ENSOR
1 section and click the R
EADING
T
RIGGER
P
ARAMETERS
button.
Edit dialog box.
Download all changes to ICR.
For connecting the “Sensor 1“ switching input via the CDB 420 or CDM 420 Connection
Module, see the “
CDB 420 Connection Module“ Operating Instructions (order no. 8 010
001, German/English version)
respectively the
“CDM 420 Connection Module“ Operating
Instructions (order no. 8 010 004, German/English version).
Note
An external pulse is not required for “Percentage Evaluation“ mode.
Fig. 5-5:
Connections of the “Sensor 1“ switching input
PNP sensor
Switch
V
S
= +15 to +30 V DC
*) V
i max
= 28 V!
ICR 84x
V
i
Switching mode
Current at the input starts the reading interval on the ICR.
(default setting: not inverted (active high), debouncing time: 10 ms,
start delay: 0 ms, stop delay: 0 ms)
Characteristics
– Optodecoupled, non-interchangeable
– Can be connected to PNP output on a sensor
Electrical values
Low:
–1 V
≤
V
i
≤
+1 V
High: +8 V
≤
|V
i
|
≤
+28 V
–0.3 mA
≤
I
i
≤
+0.3 mA
+1.4 mA
≤
|I
i
|
≤
+18 mA
Table 5-11: Characteristic data of the “Sensor 1“ switching input