Table 18:
MF1 – Speed
submenu
Parameter
Description
Limit
Sets speed switching threshold. The digital output is activated when the
current speed exceeds the set threshold. The switching hysteresis is fixed at
100 mm/s.
Options
•
50 … 15,000 [mm/s]
Factory setting
•
5,000 [mm/s]
inactive
active
Limit
Hyst
Speed
Figure 23: Representation of the
Speed
function
Limit
Speed-based switching threshold
Hyst
Hysteresis of switching threshold
Speed
Measured speed
Sign
Select the direction of travel to be monitored.
Options
•
+ / –: Monitoring in both directions of movement
•
+: Monitoring in
+
direction of movement (increasing distance)
•
–: Monitoring in
–
direction of movement (decreasing distance)
Factory setting
•
+ / –
7.1.11
MF1 – Srvice submenu
In this submenu, you can parameterize the MF1 as a switching output for pending
faults.
The switching output is activated as soon as at least one of the selected parameters
has reached the warning limit. The switching output remains active if the error limit is
reached due to continued overshoot. For more information on faults
.
For devices with integrated heating, the MF1 can also be parameterized as a switching
output for the current status of the device heating, thereby monitoring the heating
activity.
You can select several parameters. These are
OR
linked and assigned the MF1 as a
shared output.
Requirement for display:
•
more?
menu:
Yes
option
•
Menu
MFx On
:
Enable
option
•
Functn
parameter:
Srvice
option
OPERATION
7
8014755/19H8/2021-10-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP
41