RN200 user manual 25
During operation, except in the OFF/RESET mode, the controller makes periodic or “on event”
recordings, partially configurable with the programming parameters.
Four types of registrations are managed:
1. Event recordings.
2. Periodic registrations.
3. Recordings of peaks.
4. Diagnostic codes (DTC) of external devices (inverters).
The historical archives are accessible in any operating state of the controller. To enter the
archives view, use the ▲ and ▼ buttons until the basic page of the HISTORY LOGS (H.01) is
displayed.
Then press
ACK/ENTER
to view the list of archives.
Using the
▲ and ▼ buttons, select the desired historical archive. Then press the
ACK/ENTER
button to access it.
Using the ▲ and ▼ buttons, you can scroll through the different records in the archive. Each
record is identified by a number and by the date and time of storage. The number is shown in
the first line on the multifunctional display together with the total number of records and the
maximum capacity of the archive.
Each recording can use multiple pages to show all the data (depends on the type of recording):
in these cases use the ◄ and ► buttons to move between and various pages.
If the controller is in OFF/RESET mode, it is possible to "empty" the displayed archive by
holding the
ACK/ENTER
and
ESC/SHIFT
buttons simultaneously for five seconds.
Attention:
the operation is irreversible, a deleted archive cannot be recovered.
Press the
ESC/SHIFT
button to return to the list of archives or to exit the historical archives
view.