24 RN200 user manual
The total reactive power supplied by the generators (kvar).
The following lines are related to the individual generators. For each generator it shows:
Its address on PMCB (2 digits).
Its rated active power (kW).
The supplied active power (kW).
The supplied reactive power (kvar).
The engine operating hours.
This page shows the significant data of each MC (mains controller) that communicates over
the PMCB can bus. It uses one display line for each MC. If there are more than 7 MC, it shows
them all, rotating them on the display every two seconds: press and hold the
ESC/SHIFT
button to stop the rotation on the current display. If some measures are not available, they are
displayed with dashes.
The page is hidden if there are no MC controllers.
The upper part contains the total information (sum of all MC controllers). It is shown only if
there are at least two MC controllers. It contains:
The total active power imported or exported (kW).
The total reactive power imported or exported (kvar).
The following lines are related to the single MC controller. For each MC it shows:
Its address on PMCB (2 digits).
The imported or exported active power (kW).
The imported or exported reactive power (kvar).
This page shows the significant data of each RN (renewables controller) that communicates
over the PMCB can bus. It uses one display line for each RN. If there are more than 7 RN, it
shows them all, rotating them on the display every two seconds: press and hold the
ESC/SHIFT
button to stop the rotation on the current display. If some measures are not
available, they are displayed with dashes.
The page is hidden if there are no RN controllers.
The upper part contains the total information (sum of all RN controllers). It is shown only if
there are at least two RN controllers. It contains:
The total active power supplied (kW and %).
The total reactive power imported or exported (kvar and %).
The following lines are related to the single RN controller. For each RN it shows:
Its address on PMCB (2 digits).
The active power generated (kW and %). The measurement is followed by a "*" if the
RN controller is limiting the active power production of its inverters.
The imported or exported reactive power (kvar and %). The measurement is followed
by a "*" f the RN controller is limiting the reactive power production of its inverters.