RN200 user manual 11
6.5
This mode allows the display and change of the programming parameters.
WARNING! Assigning an incorrect value to one or more parameters can cause
malfunctions, damage to things or injury to people. The parameters must only be
changed by qualified personnel. Parameters may be password protected (see par.
6.5.1.1).
Each parameter (3) is associated with a 4-digit numeric code ("0116" in the example) which
allows to identify it regardless of the language used. The current value of the parameter ("400")
is shown in brackets below the description ("Renewables nominal voltage (V)").
The first line below the title bar (2), allows you to identify the current menu by means of a
numeric identifier ("1.4") and a language-dependent description ("Renewable sources"). In this
row a pair of numbers (“3/06”) is displayed on the right. The first number indicates which menu
item is selected, the second indicates how many items are present in the menu.
Pressing
ESC/SHIFT
button, the first line (1) is temporarily substituted with a status
message.
Use the ▲ and ▼ buttons to select the programming mode (press them until "PROGRAM"
appears on the display). Then press the
ACK/ENTER
button to access the programming
menus.
After this operation, the controller will show the last parameter or the last menu used by the
operator. If it is not what you want, use:
•
The ▲ and ▼ buttons to select a submenu or parameter.
•
The
ESC/SHIFT
button to go back to the upper menu.
•
The
ACK/ENTER
button to enter a submenu.
When the display shows the parameter to be modified, the current value of the parameter is
shown in square brackets, for example "[0400]". If instead it is enclosed in the symbols "<>"
(for example "<400>"), it means that you do not have the rights to modify the parameter. This
may depend on:
•
The device is not in OFF/RESET mode. In fact, most of the parameters can only be
changed in this mode.
P.05 PROGRAM _
1.4 Renewable sources ____ _3/06
0116-Renewables nominal voltage (V)
[400]
______________________________________
Access level: manufacturer_
2
3
LEGEND:
1
– Title bar
2
– Current menu
3
– Current parameter
4
– Parameter value
5
– Access level
1
4
5