Aqua Cubic Multiplex
-
MAN0004 Rev. B 29.03.99
15/33
6.2.2.c – List of codes to be programmed
For the programming and the meaning of the codes see par. 6.3. In this modality, the programming of the following
codes is recommended:
Tab. 11 – Table of the codes recommended in the modality “three alternated single columns, PPP1”
Code Meaning
011
Programming of the value of the capacity of resins exchange
020
Programming of the time and of the day of the week (non influential)
100
Programming of the volume of resin and of the percentage of reserve of the column
A
110
Programming of the litre counter divider (prescaler)
112
Programming of the regeneration cycle ( stop times ).
210
Transfer of the parameters programmed for the column
A
to the
B
and
C
010
Programming of the hardness value
220
Initialisation of the system
N.B. :
If the three columns are of the same dimensions, it is supposed that they will alsobe regenerated with the same times of
the regeneration cycle. To this end, the flag 1CP must be programmed with the value 0. If the separate programming of
the cycle times of the column B is required, (the columns A and C use the same times, programmed with the code 112),
it is necessary to add to the list of tab. 11, the code 111, and the flag 1CP must be programmed with the value 1.
In the case in which columns of different dimensions are used, the recommended programming varies as follows:
Tab. 12 – Table of the codes recommended in the modality “three alternated single columns, PPP1” of different
dimensions
Code Meaning
011
Programming of the value of the capacity of resins exchange
020
Programming of the time and of the day of the week (non influential)
100
Programming of the volume of resin and of the percentage of reserve of the column
A
101
Programming of the volume of resin and of the percentage of reserve of the column
B
102
Programming of the volume of resin and of the percentage of reserve of the column
C
110
Programming of the litre counter divider (prescaler)
111
Programming of the regeneration cycle ( stop times ) per the column
B
112
Programming of the regeneration cycle ( stop times ) for the columns
A
and
C
010
Programming of the hardness value
220
Initialisation of the system
Remember that in order to use
Aqua Cubic Multiplex
as described in tab. 12, the flag
1CP
must be programmed to
1.
6.2.3 – PPP2 – Two alternated single columns.
6.2.3.a – Operative characteristics.
This operative modality allows for the use of
two distributors, each of which connected to a single SIATA valve.
The two columns
alternate in service
, and so while one is in service, the other
will be first in regeneration and then
in stand-by
.
As soon as it is put into service, typically after having keyed in the code
220
, the column B is put into stand-by, while
the column A is put into service. The signal to the pins 43 – 44 of the terminal board will be active, while the signal to
the pins 45 – 46 for the column B will be inactive. The LED
A Service
on the panel will be on, while the LED
B
Service
will be off. The LED
A
will be on to indicate that the display is visualising the volume of the column A.