background image

5

Unusually Tight Construction

The air that leaks around doors and windows may provide

enoughfreshairforcombustionandventilation.However,in

buildings of unusually tight construction, you must provide

additional fresh air.

Unusually tight construction is

defined

as con

-

struction where:

a. walls and ceilings exposed to the outside

atmosphere have a continuous water vapor

retarder with a rating of one perm (6 x 10

-11

kg

per pa-sec-m

2

) or less with openings gasketed

or sealed 

and

b. weather stripping has been added on openable

windows and doors

and

c. caulking or sealants are applied to areas such

as joints around window and door frames,

between sole plates and

floo

rs, between wall-

ceiling joints, between wall panels, at penetra

-

tions for plumbing, electrical, and gas lines,

and at other openings.

If your home meets all of the three criteria above,

you must provide additional fresh air. See

Ventila

-

tion Air From Outdoors

, page 5.

If your home does not meet all of the three criteria

above, proceed to

Determining Fresh-Air Flow for

Appliance Location

, page lright. 

VENTILATION AIR

Ventilation Air From Inside Building 

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts.

You must provide two permanent openings: one within

12" of the ceiling and one within 12" of the

floor.

Connect

these items directly to the outdoors or spaces open to the

  

.s

e

c

a

p

s

l

w

a

r

c

d

n

a

s

c

it

t

a

e

d

u

l

c

n

i

s

e

c

a

p

s

e

s

e

h

T

.s

r

o

o

d

t

u

o

Follow the National Fuel Gas Code ANSI Z223.1/NFPA

54, Section 5.3, Air for Combustion and Ventilation for

required size of ventilation grills or ducts. 

IMPORTANT:

Do not provide openings for inlet or outlet

air into attic if attic has a thermostat-controlled power vent.

Heated air entering the attic will activate the power vent.

Outlet

Air

Ventilated

Attic

Outlet

Air

Inlet

Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic

Figure 2 - Ventilation Air from Outdoors

DETERMINING FRESH-AIR FLOW

FOR APPLIANCE LOCATION

Determining if You Ha

ve a Confined 

or Unconfined Space

Use this work sheet to determine if you have a

confined 

or unconfined space.

Space: Includes the room in which you will install appli-

ance plus any adjoining rooms with doorless passageways

or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x

height).
Length x Width x Height = cu. ft. (volume of space)
Example: Space size 22 ft. (length) x 18 ft. (width) x

8 ft. (ceiling height) = 3168 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied

with grills or openings, add the volume of these rooms

to the total volume of the space. 

2. Multiply the space volume by 20 to determine the maxi-

mum Btu/Hr the space can support.

_______ (volume of space) x 20 = (Maximum Btu/Hr

the space can support)
Example: 3168 cu. ft. (volume of space) x 20 = 63,360

(maximum Btu/Hr the space can support)

This fresh air would come from an adjoining uncon- 

fined space. When ventilating to an adjoining uncon-

of the floor on the wall connecting the two spaces      

 

fined space, you must provide two permanent open-

ings: one within 12” of the ceiling and one within 12”
(

See Figure 1).

 You can also remove door into ad-

 

 

joining room (see Figure 1). Follow the National Fuel 

Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for 

Combustion and Ventilation for required size of vent- 

ilation grills or ducts.  

Or

Remove

Door into

Adjoining

Room,

Option

3

Ventilation Grills 

Into Adjoining Room,

Option 

2

Ventilation

Grills 

Into Adjoining 

Room,

Option 

1

12"

12"

Figure 1 - Ventilation Air from Inside Building

Summary of Contents for Premier Estate PEVFR18LP

Page 1: ...pliance CONSUMER Retain this manual for future reference This appliance may be installed in an aftermarket permanently located manu factured mobile home where not prohib ited by local codes This appliance is only for use with the type of gas indicated on the rating plate This app liance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the ma...

Page 2: ...blow directlyintotheappliance Avoidanydrafts that alter burner flame patterns Ceiling fans can create drafts that alter burner flamepatterns Alteredburnerpatternscan cause sooting WARNING Do not use a blower insert heat exchanger insert or other accessory not approved for use with this appliance Due to high temperatures the appliance should be located out of traffic and away from furniture and draper...

Page 3: ...y shutoff system The ODS shuts down the fireplace if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 If appliance keeps shutting off see Troubleshooting pages 19 through 21 11 Do not run appliance where flammable liquids or vapors are used or stored under dusty conditions 12 Do not use this appliance to cook food or burn paper or other objects 13 Never pla...

Page 4: ...uel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation All spaces in homes fall into one of the following ventilation classifications 1 Unusually Tight Construction 2 Unconfined Space Theinformationonpages4through6willhelpyouclassify your space and provide adequate ventilation WARNING This heater shall not be installed in a room or space unless the required volume of indoor ...

Page 5: ...outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent Outlet Air Ventilated Attic Outlet Air Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic Figure 2 Ventilation Air from Outdoors DETERMINING FRESH AIR FLOW FOR APPLIANCE LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to ...

Page 6: ...does not meet the required volume for indoor combustion air combustion and ventilation air shall be provided by one of the methods described intheNationalFuelGasCode ANSIZ223 1 NFPA 54 the International Fuel Gas Code or applicable local codes CONTINUED VENTED OPERATION Note When used as a vented heater appliance must be installed only in a solid fuel burning fireplace with a working flue and const...

Page 7: ...ugh this is beneficial installing appliance in rooms without enough ventilation air may cause mildew to form CHECK GAS TYPE Use the correct gas type natural or propane LP for your appliance If your gas supply is not correct or if you do not know your gas type do not install appliance INSTALLATION ITEMS NEEDED Before installing appliance make sure you have the items listed below external regulator f...

Page 8: ...lator damage could occur For propane LP gas the installer must supply an external regulator The external regulator will reduce incoming gas pressure Youmustreduceincominggaspressuretobetween 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install the external regulator with the vent pointing down as shown in Figure 4 Pointing the vent down protects...

Page 9: ...nd that you install a sediment trap in supply line as shown in Figure 5 Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and appliance Locate sediment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into appliance gas controls If sediment trap is not installed or is i...

Page 10: ... valve located on or near gas meter of natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoff valve for natural gas or propane LP supply to equipment shutoff valve for propane LP Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 4 Correct all leaks at once CONTINUED 10 OPTIONAL REMOTE CONTROL SET INSTALLATION AND OPERATION COMMUNIC...

Page 11: ...Figure 7 Log Placement Savannah Oak 18 ...

Page 12: ...Figure 8 Log Placement Savannah Oak 24 and 30 ...

Page 13: ...1 2 3 4 5 6 7 13 Log Placement Premier Estate 18 Figure 9 Log Placement Premier Estate 18 Logs ...

Page 14: ...14 1 2 3 4 5 6 7 8 Log Placement Premier Estate 24 Figure 10 Log Placement Premier Estate 24 Logs ...

Page 15: ...ch must be lighted by hand When lighting the pilot appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor Do not touch any electric switch do not Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions repair may result in a fire or explosion Use only your hand to push in or turn the If you ...

Page 16: ... pilot does not light no spark contact a qual ified service person or gas supplier for repairs Until re with match see Manual Lighting Procedure page 15 8 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released contact a qualified service person or gas supplier for re for five 5 seconds see Figure 11 This w...

Page 17: ...command from any compatable remote control it captures the new address and then beeps 3 times to con firm the synchronization programming Side Slide Switch ON OFF Key Note BACKUP FUNCTION If the batteries in the transmitter Hand Set or rec eiver are low the appliance can be switched on man ually by moving the 3 position slide switch see Fig ure 14 to the ON position Replace or remove low batteries...

Page 18: ... and let cool Remove blockage Blocked burner flame holes will create soot MAIN BURNER BURNER FLAME PATTERN Figure 19 shows the correct burner flame patern Figure 20 shows the incorrect burner flame patern turn Gas Log Set off see Turning OFF the Ap pliance page 15 see Cleaning and Maintenance this page see Troubleshooting page 19 CLEANING AND MAINTENANCE WARNING Turn off Gas Logs and let CAUTION ke...

Page 19: ...create soot We recommend that you clean the unit every three months during operation and have TROUBLESHOOTING Note All troubleshooting items are listed in order of operation POSSIBLE CAUSE 1 Ignitor electrode positioned wrong 2 Ignitor electrode broken 3 Ignitor electrode not con nected to ignitor cable 4 Ignitor cable pinched or wet 5 Broken ignitor cable 6 Bad piezo ignitor REMEDY 1 Replace pilo...

Page 20: ...20 ...

Page 21: ...21 ...

Page 22: ...90945 8 Orifice NG 1 RMH 120 SP033 RMH 120 SP018 8 Orifice LP 1 RMH 120 SP051 RMH 120 SP049 9 Orifice Tube Main Burner 1 RMH 120 09003 RMH 120 09003 9 Orifice Tube Main Burner 1 RMH 120 09004 RMH 120 09004 10 Elbow 375 MNPT X 375 Flare 1 RMH 120 00062 RMH 120 00062 11 Adapter 375 MNPT X 5625 Flare 1 RMH 120 00050 RMH 120 00050 12 Adapter 375 FNPT X 5625 Flare 1 FCHD1809021 FCHD1809021 13 Tube Main...

Page 23: ...roduce the specified heat propane LP gs supply may be low You may feel your gas pressure is too low If so contact your local natural or propane LP gas supplier Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty TECHNICAL SERVICE You may have further questions about installation opera tion or troubleshooting If so contact SHM Internat...

Page 24: ... rust or discoloring of any kind use or installation contrary to instructions and applicable building codes including heating the product to temperatures above its rated specifications which can cause considerable warping disassembly including removal of the product from a built in installation damage resulting from accident alteration misuse abuse hostile environments or improper installation repa...

Reviews: