background image

6

3. Add the Btu/Hr of all fuel burning appliances in the

space.
Vent-free log set _______________ Btu/Hr
Gas water heater* ______________ Btu/Hr
Gas furnace ___________________ Btu/Hr
Vented gas heater ______________ Btu/Hr

Gas fireplace logs

______________ Btu/Hr

Other gas appliances*   + ________ Btu/Hr
Total                              = ________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent

draws combustion air from the outdoors and vents to

the outdoors.

Example:
Vent-free log set ______________ Btu/Hr
Gas water heater* _____________ Btu/Hr
Total                              = ________ Btu/Hr

4. Compare the maximum Btu/Hr the space can support with

the actual amount of Btu/Hr used.

____ Btu/Hr (max. the space can support) 
____ Btu/Hr (actual amt. of Btu/Hr used)

Example: 63,300 Btu/Hr (maximum the space can sup-

port)
73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a

confined

space because

the actual Btu/Hr used is more than the maximum Btu/Hr

the space can support. You must provide additional fresh

air. Your options are as follows:
A. Rework work sheet, adding the space of an adjoining room.

If the extra space provides an

unconfined

space, remove

door to adjoining room or add ventilation grills between

rooms. See Ventilation Air from Inside Building, page 5.

B. Vent room directly to the outdoors. See Ventilation Air

from Outdoors, page 5.

C. Install a lower Btu/Hr appliance, if lower Btu/Hr size

makes room unconfined. 

If the actual Btu/Hr used is less than the maximum Btu/Hr

the space can support, the space is an

unconfined

space.

You will need no additional fresh air ventilation. 

39,000
40,000
79,000

AIR FOR COMBUSTION 

AND VENTILATION

WARNING: If the area in which the

heater may be operated does not meet the

required volume for indoor combustion

air,combustion and ventilation air shall be

provided by one of the methods described

intheNationalFuelGasCode,ANSIZ223.1/

NFPA 54, the International Fuel Gas Code,

 

or applicable local codes.

CONTINUED

VENTED OPERATION

Note: When used as a vented heater, appliance must be

installed only in a solid-fuel burning fireplace with a

working flue and constructed of noncombustible mat-

erial.

Area of Various Standard

Round Flues

Diameter (ins.)

Area (sq. ins.)

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

Follow instructions 

Installing  Damper Clamp

 on 

page 8 for location of damper in the fireplace.

Damper

Clamp

Damper

Chimney

Minimum Permanent

Height (ft.) Flue Opening (sq. ins.)

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

Figure 2 - Damper Clamp

The

Nationa

l

FuelGasCode

,

 A N SI Z223.1/NFPA 54

 defines a confined space as a space

whose volume is less than 50 ft

3

per 1000btu/hr (4.8 m

3

 per kw) of the aggregate input

of all appliances installed in that space. Rooms communicating directly with the space 

in which the appliances are installed, through openings not furnished with doors are 

considered a part of the unconfined space.  

You may also use this heater as a vented product. There are

three reasons for operating your heater in the vented mode.

1. The fireplace does not meet the clearance to com-

bustibles requirements for vent-free operation.

2. State or local codes do not permit vent-free operation.
3. You prefer vented operation.

manently open chimney flue damper. You must install the

damper clamp. This will insure vented operation (see Fig- 

u r e 3 on page 8).  The damper clamp will keep damper

opening

you must provide. Attach damper clamp so the minimum

permanentflue opening will be maintained at all times.

open. See chart below for minimum permanent flue

If reasons number 1 or 2 above apply to you, you must per-

Summary of Contents for Premier Estate PEVFR18LP

Page 1: ...pliance CONSUMER Retain this manual for future reference This appliance may be installed in an aftermarket permanently located manu factured mobile home where not prohib ited by local codes This appliance is only for use with the type of gas indicated on the rating plate This app liance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the ma...

Page 2: ...blow directlyintotheappliance Avoidanydrafts that alter burner flame patterns Ceiling fans can create drafts that alter burner flamepatterns Alteredburnerpatternscan cause sooting WARNING Do not use a blower insert heat exchanger insert or other accessory not approved for use with this appliance Due to high temperatures the appliance should be located out of traffic and away from furniture and draper...

Page 3: ...y shutoff system The ODS shuts down the fireplace if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 If appliance keeps shutting off see Troubleshooting pages 19 through 21 11 Do not run appliance where flammable liquids or vapors are used or stored under dusty conditions 12 Do not use this appliance to cook food or burn paper or other objects 13 Never pla...

Page 4: ...uel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation All spaces in homes fall into one of the following ventilation classifications 1 Unusually Tight Construction 2 Unconfined Space Theinformationonpages4through6willhelpyouclassify your space and provide adequate ventilation WARNING This heater shall not be installed in a room or space unless the required volume of indoor ...

Page 5: ...outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent Outlet Air Ventilated Attic Outlet Air Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic Figure 2 Ventilation Air from Outdoors DETERMINING FRESH AIR FLOW FOR APPLIANCE LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to ...

Page 6: ...does not meet the required volume for indoor combustion air combustion and ventilation air shall be provided by one of the methods described intheNationalFuelGasCode ANSIZ223 1 NFPA 54 the International Fuel Gas Code or applicable local codes CONTINUED VENTED OPERATION Note When used as a vented heater appliance must be installed only in a solid fuel burning fireplace with a working flue and const...

Page 7: ...ugh this is beneficial installing appliance in rooms without enough ventilation air may cause mildew to form CHECK GAS TYPE Use the correct gas type natural or propane LP for your appliance If your gas supply is not correct or if you do not know your gas type do not install appliance INSTALLATION ITEMS NEEDED Before installing appliance make sure you have the items listed below external regulator f...

Page 8: ...lator damage could occur For propane LP gas the installer must supply an external regulator The external regulator will reduce incoming gas pressure Youmustreduceincominggaspressuretobetween 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install the external regulator with the vent pointing down as shown in Figure 4 Pointing the vent down protects...

Page 9: ...nd that you install a sediment trap in supply line as shown in Figure 5 Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and appliance Locate sediment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into appliance gas controls If sediment trap is not installed or is i...

Page 10: ... valve located on or near gas meter of natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoff valve for natural gas or propane LP supply to equipment shutoff valve for propane LP Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 4 Correct all leaks at once CONTINUED 10 OPTIONAL REMOTE CONTROL SET INSTALLATION AND OPERATION COMMUNIC...

Page 11: ...Figure 7 Log Placement Savannah Oak 18 ...

Page 12: ...Figure 8 Log Placement Savannah Oak 24 and 30 ...

Page 13: ...1 2 3 4 5 6 7 13 Log Placement Premier Estate 18 Figure 9 Log Placement Premier Estate 18 Logs ...

Page 14: ...14 1 2 3 4 5 6 7 8 Log Placement Premier Estate 24 Figure 10 Log Placement Premier Estate 24 Logs ...

Page 15: ...ch must be lighted by hand When lighting the pilot appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor Do not touch any electric switch do not Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions repair may result in a fire or explosion Use only your hand to push in or turn the If you ...

Page 16: ... pilot does not light no spark contact a qual ified service person or gas supplier for repairs Until re with match see Manual Lighting Procedure page 15 8 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released contact a qualified service person or gas supplier for re for five 5 seconds see Figure 11 This w...

Page 17: ...command from any compatable remote control it captures the new address and then beeps 3 times to con firm the synchronization programming Side Slide Switch ON OFF Key Note BACKUP FUNCTION If the batteries in the transmitter Hand Set or rec eiver are low the appliance can be switched on man ually by moving the 3 position slide switch see Fig ure 14 to the ON position Replace or remove low batteries...

Page 18: ... and let cool Remove blockage Blocked burner flame holes will create soot MAIN BURNER BURNER FLAME PATTERN Figure 19 shows the correct burner flame patern Figure 20 shows the incorrect burner flame patern turn Gas Log Set off see Turning OFF the Ap pliance page 15 see Cleaning and Maintenance this page see Troubleshooting page 19 CLEANING AND MAINTENANCE WARNING Turn off Gas Logs and let CAUTION ke...

Page 19: ...create soot We recommend that you clean the unit every three months during operation and have TROUBLESHOOTING Note All troubleshooting items are listed in order of operation POSSIBLE CAUSE 1 Ignitor electrode positioned wrong 2 Ignitor electrode broken 3 Ignitor electrode not con nected to ignitor cable 4 Ignitor cable pinched or wet 5 Broken ignitor cable 6 Bad piezo ignitor REMEDY 1 Replace pilo...

Page 20: ...20 ...

Page 21: ...21 ...

Page 22: ...90945 8 Orifice NG 1 RMH 120 SP033 RMH 120 SP018 8 Orifice LP 1 RMH 120 SP051 RMH 120 SP049 9 Orifice Tube Main Burner 1 RMH 120 09003 RMH 120 09003 9 Orifice Tube Main Burner 1 RMH 120 09004 RMH 120 09004 10 Elbow 375 MNPT X 375 Flare 1 RMH 120 00062 RMH 120 00062 11 Adapter 375 MNPT X 5625 Flare 1 RMH 120 00050 RMH 120 00050 12 Adapter 375 FNPT X 5625 Flare 1 FCHD1809021 FCHD1809021 13 Tube Main...

Page 23: ...roduce the specified heat propane LP gs supply may be low You may feel your gas pressure is too low If so contact your local natural or propane LP gas supplier Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty TECHNICAL SERVICE You may have further questions about installation opera tion or troubleshooting If so contact SHM Internat...

Page 24: ... rust or discoloring of any kind use or installation contrary to instructions and applicable building codes including heating the product to temperatures above its rated specifications which can cause considerable warping disassembly including removal of the product from a built in installation damage resulting from accident alteration misuse abuse hostile environments or improper installation repa...

Reviews: