- 29 -
Caution: Physical and Secondary Damage
•
If using the equipment as a power source for medical equipment, you
must check with the medical equipment manufacturer, doctor and
hospital before using the equipment.
•
Set the frequency in accordance with the devices using the equipment.
1) Switch the frequency selector in accordance with the devices using the
equipment.
(
Refer to section "5-9
.
Frequency Selector" .
)
2) Turn off the switches of devices being used.
3) Turn all breakers (main, 3-P and 1-P) to "OFF".
4) Start the engine.
(
Refer to section "7-1
.
Starting the Engine".
)
5) Check the frequency with a frequency lamp.
6) Connect the power plug(s) of device(s) being used to the AC output
receptacle(s).
7) Turn all breakers (main, 3-P and 1-P) to "ON".
(Check that the ELCB lever is set to "ON" .)
<<<<
Note
>>>>
•
During operation, the 3-phase output voltage of the AC power source is constantly
displayed by the AC meter voltage display regardless of whether the breaker is set
to "ON" or "OFF" .
■
Recovery from Overcurrent Breaker Operation
Caution: Injury
•
Always be sure to turn off the power switches of all devices using the
equipment when turning on the equipment breakers. Leaving on the
power switch of a device using the equipment when the equipment
breakers are turned on could result in the sudden operation of the
corresponding device.
Breakers operate when there is excessive current to isolate the corresponding
circuit.
Inspect the breakers if a device being used stops during equipment operation.
Frequency Lamp
1-P Breaker
Main Breaker
3-P Breaker
ELCB