38
Spill Containment Cleaning/Inspection
Use a high-pressure cleaner or similar equipment to clean the inside of the spill
containment.
Remove the drain plug (R1
”) to drain the cleaning water.
Check that there no rust has developed inside of the spill containment. If rust has
developed, remove the rust and clean again.
Tentatively, apply sealant coating to the
plug (R1”) or wrap it in seal tape and reinsert it.
Allow water to accumulate and check that the spill containment has no internal leakage.
R
emove the drain plug (R1”) to drain the water.
After the procedures have been completed, apply sealant coating to
the plug (R1”) or
wrap it by seal tape and reinsert it.
< Note >
If the fluid drained when cleaning the spill
containment contains oil or grease, dispose of it
according to the related laws and regulations.
If the spill containment has a leak, contact the
authorized distributor where the generator was
purchased.
1
Drain Plug
(R1”)
Lifting Hook
Bolt
Wire Connector
Position B
Union Joint
Fuel Tank
Spill Containment
2
3
4
5
6
7
Bolt
Washer
Washer