25
< Note >
Check that the surrounding area is safe before starting the engine.
When there are multiple workers who are working together, they must mutually signal each other
before starting the engine.
Do not use in an area with high temperature or humidity, or an area with a large amount of dust.
Do not open any doors during operation. Operating with door open can negatively affect cooling
effect, resulting in an equipment malfunction.
Use ear protection if the level of noise is high. Failure to do so could result in hearing damage.
Please be careful about a strong wind and the opening and shutting of the door. If a door is
opened suddenly and is closed, a finger might be sandwiched.
(1) Manual Start
Turn off the main breaker on the operation panel of this machine.
Set the ACCESSORY switch to OFF, and use the safety cap to cover it.
Open the fuel valves.
Set the STARTER SWITCH selector to START position.
< Note >
The warm-up process starts automatically.
Please keep in mind that the muffler may emit some smoke when engine is started.
Never turn accessory switch ON during operation.The engine keeps running while accessory
Switch is ON
Use the VOLTAGE REGULATOR dial to adjust the voltage to the specified value.
60Hz
240V
Turn on the breaker to activate power supply.
5
6
1
2
3
4
Fuel
Filter
Fuel Valves
Water
Seperator
Main
Breaker
Accessory Switch
Starter Switch
Voltage Regulator
Open
Open
Close
Close
Remote Start Terminal
Summary of Contents for DGK14F
Page 2: ......
Page 47: ...44 13 Generator Circuit Diagram...
Page 48: ...45 14 Engine Electrical Circuit Diagram...
Page 49: ......
Page 50: ...2019...