10
5. Equipment
5-1. Available Output Monitor
The available generated output for each output power source is displayed digitally. You can
use the display selector switch to change the display in the following order: Total output of
240V Receptacle and 240/120V Receptacle, 120V Receptacles output. Total output of 240V
Receptacle and 240/120V Receptacle is always displayed when the engine is started.
< Note >
Consider the digitally displayed available output as an
approximate estimate. Be sure to thoroughly consider the
displayed value and the used load capacity when using a load
such as a motor with large starting capacity.
If “- -” is displayed for the available output, it means that usage
has exceeded the rated capacity. Immediately stop the
equipment being used and reduce the load capacity of the
equipment.
5-2. Spill Containment
The bed of this generator is equipped with a spill containment (structure for preventing
leakage of liquids) so that any spilled liquid will not leak to outside of the generator when oil or
fuel is spilled or leaks. Before starting operation, check if there is accumulated liquid in the
spill containment. Flush out any liquid that has accumulated.
(
Refer to section “
8-4
. Checking the Spill Containment” for inspection procedures. )
(
Refer to section
“
10. Inspection/Maintenance (9) Flushing Liquid in Spill Containment
”
for flushing procedures. )
The generator is equipped with the following in order to prevent liquid from spilling in case you
forget to flush the liquid: The operation panel is equipped with an indicator that illuminates
when its sensor is triggered as the spill containment capacity accumulated enough liquid to
reach to about 4.5gal(17 liters).
If the liquid stored in the spill containment exceeds approximately about 13.4gal(51 liters)
during operation, the SPILL CONTAINMENT overflow warning indicator illuminates, and the
engine will be automatically stopped. If this occurs, flush the liquid stored in the spill
containment.
(Refer to section “
10. Inspection/Maintenance (9) Flushing Liquid in Spill Containment
”.)
WARNING : INJURY
Do not open the check door when the starter switch is in the AUTO or START
position. It will cause injury by rotating parts such as cooling fans and fan belt.
Always turn the starter switch to the STOP position and stop the engine,
then close and lock OPERATION PANEL DOOR before checking or
maintaining the engine or any equipment.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after
stopping the engine as they are still extremely hot.
CAUTION : FIRE
If fuel or oil leaks , repair the leaking location before operating.