45
The voltage drops drastically
when connecting to load
1.
AVR is defective
2.
Unbalanced loads sharing to
each terminal
3.
Wrong frequency is used
4.
Loads total exceeds the rated
current
5. AVR protective device has
activated
1.
Ask our distributor to repair
2.
Balance the loads sharing to
each terminal
3.
Set the switch to the load
frequency
4.
Decrease the loads to meet
the rated output
5.
Press the AVR reset button
to release the protective
device
Cannot turn the breaker to ON 1. The Main breaker positions at
between ON and OFF
2.
Short circuit on the load
1.
Once turning the lever to
OFF, turn it to ON
2.
Check the load circuit
Controller does not turn on
1.
Battery output is weak
2.
Battery is deteriorated
3.
Battery terminal is OFF or
loose
4.
Battery terminal is corroded
5.
Fuse is blown
6.
Disconnected circuit, loose
terminal or departed
7.
Controller or Power Switch is
defective
1.
Check/ battery liquid/ or
Change
2.
Change battery
3.
Fix/Tighten terminal
4.
Clean terminal
5.
Check/Change fuse
6.
Ask our distributor to repair
7.
Ask our distributor to repair