(4) Drain water in the Water Sedimentor
When a float (red) in the cup is floating at
drain level, drain water.
Loosen the Cock.
After draining finishes, tighten the
Cock.
< Note >
After draining finishes, extract the air in fuel line.
(Refer to
『
9-2. Procedures during Operation
』
.)
(5) Maintenance of the Fuel Filter
Loosen the fixing screw of the Fan Guard
located on the side of the Fuel Filter.
Remove the Fan Guard.
Disassemble Fuel Filter using filter wrench.
Drain the remaining water from the Filter.
Apply little amount of the diesel fuel onto
new Fuel Filter Gasket.
Tighten the Fuel Filter using finger until the filter
gently seated to the bracket,
Then tighten the Filter 2/3 rotation using fuel filter wrench.
Reassemble the Fan Guard to the original position with fixing screw.
< Note >
Do not operate the generator without reassembling the Fan Guard to avoid injury.
After draining finishes, extract the air in fuel line.
(Refer to
『
9-2. Procedures during Operation
』
.)
Fuel Filter Part No.
Isuzu Part No.
1132400791
Check
Startup
Clean
Every 200 hours
Drain
Every 200 hours
Change
Every 500 hours
1
2
2
1
Cock
Cup
Float
Water Drain Level
Fuel Filter
Fan Guard
3
4
5
6
Gasket