92
External analogue input (AI) (option)
(1) Number of input
(2) Allotment function
(3) Input rating
(4) Accuracy
(5) Sampling period
(6) Scaling
(7) AI Filter
(8) AI offset
(9) AI gain
(10) PV-AI Characteristics correction
1ch
Execution SV、EV1~4、DO 1~6 level、OUT1~2 Upper and lower limiter、
PV Off set、 Manual output
4-20mA (Reception resistance100
Ω
)
0-10V (Input resistance about 500k
Ω
)
±0.1%FS
0.2, 0.667, 1, 2 sec
-20000~30000 reserve scaling permitted (within a setting range)
0~10000 sec
±5000 unit
±5.000 %
11point ±32000 digit
External analogue output(AO) (option)
(1) Number of output
(2) Allotment function
(3) Current
(4) Voltage
(5) Output accuracy
(6) Scaling
(7) Limiter
(8) Output resolution
(9) Output renewal period
1ch
PV、 Execution SV、 OUT1、OUT2、CT1、CT2、DEV
4-20mA DC (Max load 300
Ω
) load regulation ±0.05%FS
0-10V DC (Max load 2mA)
±0.1%FS (±0.2%FS at PV output)
Within measuring range or output range
0.0~100.0 % (reserve setting permitted)
About 1/50000
50, 166.7, 250, 500 msec
Current sensor input(CT1,2)(option)
(1) Number of input
(2) Detection method
(3) Detection range
(4) Sampling period
(5) Detection accuracy
(6) Detection delay time
(7) Alarm output
(8) Detection object
(9) Setting range
(10) Recommended CT sensors
(11) Other condition
2ch
Current judging system by CT sensor
0.0~55.0A
100m sec
±3%fs
0.1~1000.0 sec (resolution 0.1sec)
Assigned to event
Assigned to OUT1、OUT2、EV1、EV2、EV3、EV4
0.0~50.0A (Default 0.0)
U_RD co., CTL-6-L CTL-6-V CTL-6-P-H CTL-6-S-H CTL-12L-8
Exclusive selection option of Feedback input
Feedback input (FB) (Servo control option)
(1) Potentiometer rating
(2) Input accuracy
(3) Sampling period
(4) Zero span adjustment
(5) FB filter
Any between 100
Ω
and 2k
Ω
/ three-wire type
±1%FS
100m sec
Manual and Auto
0~10000 sec