19
Auto
:
Manual
:
Press
key for 3 seconds, then it shifts to Action mode2 screen, when the program
control option is added on this screen, FIX (constant value control) ←→PROG
(program control) switchover is possible choose(Choose a program, then Monitor LED's
PRG lights up.
Press
key for 3seconds then it shift to Action mode 1.
Priority is given to DI function ,when PROG is allotted to external control input. DI. Key
operation cannot be performed unless allotment is canceled.
Press key then it shift to Output 1 monitor screen.
When measuring range, a unit, scaling, and output characteristics are changed, parameter
will be initialized and
(
) is display.
Output 1 monitor screen
Manual output setting range : 0.0-100.0% (within output limiter)
At the time of automatic output, monitor display only.
Refer to automatic ⇔ manual switch over, and setting method at the time of manual
operation.
A manual output is canceled when an operation mode is made into
(
).
When a power source is intercepted and re-switched on, it returns to the condition
just before intercepting.
When
is allotted to DI, DI is given priority. Automatic ⇔ manual
switchover is not performed with key operation, and only the output value at the time
of manual operation can be changed.
During AT executing or Key lock level 3-4 are set, setting is impossible
Output2 monitoring screen
Contents are the same with that of an output 1
Output 2 monitoring screen displays only when output 2 option is added.
CT1 monitor
Display range:0.0~55.0A
Displays at the time of CT input option addition, and the current value detected by
CT Sensor is displayed.
Upper Display: PV value
Middle Display: Current value
Lower Display: Detected CT sensor (CT1)