20. Common specifications
□
Type :
PAC18
□
Control element configuration
: Thyristor x 2 inverse-parallel connection
□
Main/control power supply
: 100 – 240V AC, 5VA (main/control power supply used by same phase)
□
Voltage fluctuation tolerance
: Max. ±10% of rated voltage
□
Rated frequency
: 45 – 65Hz
□
Rated current
: Any one of 6 types (20, 30, 45, 60, 80, 100A)
□
Minimum load current
:
0.6A
□
Control output range
: 0 – 98% or more
□
Applicable load
: Resistance load or inductive load (transformer primary control: phase control or complex control)
□
Control type
: Phase control, cycle calculation zero voltage switching control, complex control (specify when ordering)
(No output feedback function)
P: Phase control (specify when ordering); phase angle proportional output (P0-),
voltage proportional output (P1-) or voltage square proportion Output (P3-)
C1-: Cycle calculation zero voltage switching control
X1-:
Complex control (phase control when output increases from 0%, followed by cycle calculation zero voltage switching control)
□
Cooling
: Self cooling
□
Protection :
1) Electronic overcurrent gate cutoff circuit (optional); alarm output when operating, detection by current sensor (CT)
2) Rapid fuse (sold separately)
3) Hardware error detection (optional); detects short circuit or thyristor shorting when output is 0%
□
Control input
: Selection of any one of 3 types (current 4 – 20mA DC [receiving impedance 100
Ω
] or voltage 1 – 5V,
0 – 10V DC [input resistance 200k
Ω
]) Contact 2-position control (on/off control)
□
Standard functions
•
External adjuster
: Can be allocated to ramp, current limiter, manual operation and up to 3 external adjusters (sold separately)
•
Variation limit
: 0.0 – 99.9 sec. variable setting (set by front surface key switch)
(slow-up, slow-down) Time required to reach 0 – 100% output time, initial value:1.0 sec.
□
Additional functions (optional)
•
Output current detection function (built-in current sensor CT)
•
Current limit function
: Phase control only supported
Using pure metal load, etc., inrush current limitation, response time 0.1 sec. or less (initial value 100% or rated current)
0 – 100% of rated current set by external adjuster (current limiter) or 0 – 120% of rated current set by front panel
key operation
•
Overcurrent error alarm : Electronic overcurrent gate cutoff circuit, outputs alarm when it detects that output current value is in excess of
130% of the rating
•
Hardware error alarm
: Alarm is output when thyristor error (thyristor device is shorted and current flows even though output is 0%) is detected.
•
Heater break alarm
: Heater break is detected and alarm is output.
Heater break judgment 0 – 100% setting
[caution]: Variable resistance heaters can be controlled applicable load, but Heater break alarm function can
not be detected rightly in some cases because the change of resistance value is too large.
•
Alarm output
: One point a-contact 240V AC, 1A (insulated from system circuit)
Power failure, overcurrent error, hardware error, heater break selection
alarm contact output; redundant selection possible
•
Parameter setting function
: Separately sold data communication adapter can be connected.
you can connect to a computer via a separately sold data communication adapter and display various settings,
control input values, output values and trend graph.
•
Communication : RS-485 specs., insulated from control input and system
Communication protocol: MODBUS protocol (RTU)
Communication speed: 19200/ 9600bps
Parity: Selection of NON / EVEN / ODD
Stop bits: 1/2 selection
Power on/off, output control, ramp setting
Operation on/off, control input, operation amount, load current, alarm status can be obtained
□
Separately sold goods
•
Data communication adapter
: Model: S5009
-
Connected to computer by USB; enables various settings, control input values display,
output values display and trend graph
•
External adjuster
: Model: QSV003
-
B characteristics, 10k
Ω
, 3 lines
• External rapid fuse / fuse holder
: Protects thyristor and power equipment from load short, etc. (For model, see ‘12-1. Rapid fuse.’)
•
Noise filter
: Model
20A/30A : HF2030A-XB
45A
: HF2050A-XB
60A
: HF2060A-XB
80A
: HF2080A-XB
100A
: HF2100A-XB