4. Setup location
The device is designed to be used under the following conditions. Observe the following environmental conditions when using:
1) Indoor use
2) Elevation: Max. 2000 m (see ‘14-2. Ambient temperature and load current.’)
3) Temperature range: -10
−
55°C (see ‘14-2. Ambient temperature and load current.’)
4) Humidity range: Max. 90% RH Must be no dew condensation.
5) Transient overvoltage category: II
6) Pollution class: 2 (IEC 60664)
CAUTION
Do not use in the following locations. Doing so could lead to equipment failure, damage or fire.
• Places exposed to flammable or corrosive gases, oil mist, or excessive dust that could cause insulation to deteriorate
• Places subject to vibration or impact
• Places exposed to water dripping or direct sunlight
• Places directly exposed to air from heater or air conditioner
• Places where maintenance cannot be performed safely
5. Mounting
Fasten to control panel, wall, rack, etc., when using. To ensure safety, arrange so that people cannot easily come into contact with the equipment.
Be sure to mount vertically to allow heat to dissipate. Provide at least 100 mm of clearance above and below the device.
If the device has to be mounted horizontally, operate at no higher than 50% of the current capacity of this device.
5-1. Mounting method and clearance
Provide the clearance shown in the figure.