background image

 

-21-

 

Standard screens are indicated by a solid line box 

     

 and optional 

screens are indicated by a dotted line box 

     

 

Optional screens may not be displayed depending on the product specifications. 
 

0. Monitor screen group

                                         

 

Screen group that displays data such as voltage, current and input values of various loads 
 

0-0. Output monitor (basic screen)                                                 

 

Basic screen for the device. 
Displays current output.

 

 

When phase control (phase angle proportional control) is selected:  Output phase angle (%) 
When phase control (voltage proportional control) is selected: 

Output voltage (%) 

When phase control (voltage square proportional control) is selected:  Output power (%) 
When cycle calculation zero voltage switching control is selected:  Output operation amount (%) 
When complex control is selected:   

Output operation amount (%) 

 
Switches from this screen to various parameter groups for checking/setting 
various parameter settings. 



   

range: 0.0 – 100%   

(fractional digits below decimal point not displayed for 100%) 

 

Switches to subsequent screen 

 key sequence ‘0-1’ 

 

Pressing and holding 1.5 seconds switches to user parameter group 

 

key sequence ‘1-0.’ 

 

Pressing and holding 1.5 seconds switches to initial setting screen group 

 

key sequence ‘2-0.’ 

 

Pressing and holding 1.5 seconds switches to manual output screen group 

   

key sequence ‘3-0.’ 

                                                                     

0-1. Load current (optional)                                                                                   

            

Displays load current value (A). 

 



 

Range: At least 5% of rated current 

(Fractional digits below decimal point not displayed for 100 A or more) 



   

Displayed when current is below 5% of the rating. 

                                                                     

0-2. Control input                                                                                         

Displays control input value.   
Controls according to power supply frequency, so it can’t handle faster variation. 



 

range: -10.0 – 110%   

              (fractional digits below decimal point not displayed for 100% or more) 



 or 



  is displayed if control input is less than -10%; 



 is 

displayed if 110% is exceeded. Differs according to type of control input.   
If set to contact 2-position control (on/off control), 



  is displayed for 

C3-C2 terminal short and 



  is displayed for C3-C2 terminal open.

 

                                                                     

0-3. VR1 operation amount                                                                                         

Operation amount of VR1 is displayed in the range of 0 – 100%. 
Set either key sequence ‘1-7. Ramp lower limit setting, ’

 

key sequence ‘1-8. 

Ramp higher limit option,’ or key sequence ‘1-11. Current limiter.’ 



 

range: 0.0 – 100%   

(fractional digits below decimal point not displayed for 100%) 

                                                                     

0-4. VR2 operation amount                                                                                 

Operation amount of VR2 is displayed in the range of 0 – 100%. 
Set either key sequence ‘1-7. Ramp lower limit setting, ’ key sequence ‘1-8. 
Ramp higher limit option,’ or key sequence ‘1-11. Current limiter.’ 



 

range: 0.0 – 100%   

(fractional digits below decimal point not displayed for 100%) 

                                                                     

0-5. VR3 operation amount                                                                                     

Operation amount of VR3 is displayed in the range of 0 – 100%. 
VR3 is used for manual operation. 



 

range: 0.0 – 100%   

(fractional digits below decimal point not displayed for 100%) 

                                                                     

 

  Switches to key sequence ‘0-0. Basic screen.’ 

 
 

1. User parameter screen group

                               

The user can modify the control operation parameters.   
You can obtain safer, more reliable control characteristics by various type 
of alarm output settings and settings such as overcurrent limit. 
 
The user parameter screen group is accessed by pressing and holding 

 

for at least 1.5 seconds from key sequence ‘0-0. Output monitor (basic screen).’ 
 

 

 

Switches parameters. 

 

Enters selection. 

 

1-0 User parameter screen                                                                           



 

Displays the initial screen of the user parameter screen group.   
Switch to this screen when returning to the basic screen from the user 
parameter screen group. 

 

Switches to subsequent screen 

 key sequence ‘1-1’ 

                                                                     

1-1. Key lock                                                                                                 

Limits operation of parameters screens. 



                   

             

 

 

Initial value:

 



 

                          



User screen group other than key lock and 

 

     

     

 

initial screen group operation disabled 

                         



All parameter screen operation enabled

 

                                 
                                                     

Entered by 

 

                                                                     

1-2. Complex control phase angle adjustment                                 
    (enabled when complex control selected)

                

 

This screen is displayed when complex control is selected as a product 
specification. 
May produce delay in current phase due to load and transformer used.   
This could upset magnetic balance of the transformer, cause the transformer 
to become saturated, and excessive current could flow. This can be avoided 
by adjusting to eliminate current imbalance. Adjust while monitoring the 
waveform of the transformer load current with an oscilloscope, etc., using an 
actual load. See ‘16-6. Complex control phase angle adjustment.’

 

 



                   

 

               

       



         

Initial value: 10.0 

                       

 

       

 

Range: 0.0 – 30.0 

                                                     

Entered by 

 

 

                                                                     

1-3. Power failure error alarm (optional)                                                     

Sets whether or not to output an alarm when a power failure occurs.

 



                   

                 

Initial value: 



 

                         



Allotted to alarm output 1 

             

     

     

 

                         



Alarm not output 

                                                     

Entered by 

 

                                                                     

1-4. Overcurrent error alarm (optional)                                           

      

Sets whether or not to output an alarm when overcurrent protection circuit 
is triggered. 



                   

                 

Initial value:



 

                         



Allotted to alarm output 1

 

             

     

     

 

                         



Alarm not output

 

                                                     

Entered by 

 

                                                                     

Summary of Contents for PAC18 Series

Page 1: ...Do not supply power when wiring Doing so could result in electrical shock 5 Do not touch terminal elements or other charged parts while conducting electricity Also do not introduce foreign objects or...

Page 2: ...ter break alarm function 13 12 1 Rapid fuse sold separately 13 12 2 Heater break alarm function optional 14 12 2 1 Operation overview 14 12 2 2 Setting method 14 12 2 3 Precautions when setting 14 13...

Page 3: ...lation zero voltage switching control P0 C1 X1 3 4 6 9 Voltage 1 5V DC input resistance 200 built in contact common Current 4 20mA DC receiving impedance 100 built in contact common Voltage 0 10V DC i...

Page 4: ...ontrol power supply input terminal 100 240 V AC B characteristic 10k Display Status display red 1 digit Displays parameter screen group and alarm contents Parameter display green 3 digits Displays par...

Page 5: ...5 3 External dimensions terminal dimensions weight 20 30A Weight Approx 0 8 kg Unit mm 45 60A Weight Approx 1 8 kg Unit mm 80 100A Weight Approx 3 0 kg Unit mm...

Page 6: ...r corrosive gases oil mist or excessive dust that could cause insulation to deteriorate Places subject to vibration or impact Places exposed to water dripping or direct sunlight Places directly expose...

Page 7: ...in circuit wiring 7 1 Wiring Open the terminal block cover to connect wires to the terminal block Loosen the fastening screws mounted on the device and wire 7 2 Power supply and load main circuit wiri...

Page 8: ...ve Controller PAC18 C1 C2 Voltage current Connection with contact output controller Controller PAC18 C2 C3 On off signal If connecting with on off signal connect between C3 and C2 8 2 Multiple units c...

Page 9: ...yed Output is automatically reset if abnormal state is eliminated Set key sequence 1 3 Power failure alarm when outputting power failure alarm to optional alarm contact output AL 10 2 Overcurrent Curr...

Page 10: ...displayed in the alarm display of the left LED digit The key sequence 0 0 Output monitor basic screen display does not display less than 0 or more than 100 If control input is less than 10 the key seq...

Page 11: ...adjuster output cannot be changed by variation limit of key sequence 1 10 Variation limit 11 2 Ramp lower limit base power adjustment Set adjustment target by key sequence 1 7 Ramp lower limit setting...

Page 12: ...ts the thyristor if using loads with large inrush current such as pure metal heaters or lamp heaters Detects output current by built in CT and produces delay time to control the control angle of the t...

Page 13: ...set Rapid fuse Fuse holder QSF006 20 30A 350GH 50UL Hinode Electric Co Ltd 45 60A 350GH 100UL Hinode Electric Co Ltd Separately sold part type 80 100A CF5R06 150 Fuji Electric FA Components Systems C...

Page 14: ...break do so with device output set to maximum within the output range actually used If set outside the actually used output range or when output is small load current is less than 25 of the rated cur...

Page 15: ...down by Manual operation can be conducted by key sequence 3 1 Manual operation 2 Manual operation by external adjuster VR3 Shorting the C2 C3 terminals selects external adjuster VR3 In this case the m...

Page 16: ...characteristics 10 0 50 55 100 90 Elevation m Load current Elevation load current characteristics 0 2000 100 80 500 14 3 Control type and output waveform The device includes phase control and cycle ca...

Page 17: ...tional output You can obtain output voltage proportional to control input signal The current limit function is necessary for large inrush current loads 14 4 3 Phase control voltage square proportional...

Page 18: ...harmonic wave voltage check the power supply waveform 16 Precautions for inductive load Transformer usage objective 1 To match voltage when heater voltage differs from power supply voltage 2 When it...

Page 19: ...le adjustment is required for complex control With complex control slow up is conducted by phase control ahead of cycle calculation zero voltage switching control to cancel magnetic flux imbalance of...

Page 20: ...quence 18 1 Screen sequence Standard screens are indicated by a solid line box and optional screens are indicated by a dotted line box Optional screens may not be displayed depending on the product sp...

Page 21: ...imal point not displayed for 100 0 4 VR2 operation amount Operation amount of VR2 is displayed in the range of 0 100 Set either key sequence 1 7 Ramp lower limit setting key sequence 1 8 Ramp higher l...

Page 22: ...key setting ramp higher limit cannot be set below ramp lower limit For VR setting ramp lower limit drops if ramp upper limit is lower than ramp lower limit If the difference between ramp higher limit...

Page 23: ...reen is displayed if you have selected communication optional Displays communication protocol MODBUS RTU 1 14 Communication address optional This screen is displayed if you have selected communication...

Page 24: ...nals are shorted When communication manual output operation be enabled the manual output screen group can not be selected by key operation When Contact 2 position control input be selected the manual...

Page 25: ...ristics resistance value B 10k Lead Vinyl lead 1 m M3 crimp terminal Scale plate knob 1 each provided External dimensions and mounting method unit mm 19 2 External rapid fuse 20 30A Model QSF006 80 10...

Page 26: ...al dimensions unit mm 80 100A Model QSH003 External dimensions unit mm Insulation board 41 65 26 4 5 18 2 65 1 1 2 4 1 5 35 3 4 27 22 17 8 8 1 5 4 3 2 3 5 2 M6 17 8 16 26 1 132 116 102 70 48 16 72 13...

Page 27: ...ure metal load etc inrush current limitation response time 0 1 sec or less initial value 100 or rated current 0 100 of rated current set by external adjuster current limiter or 0 120 of rated current...

Page 28: ...nce Between control power supply terminals and control input terminals 500V DC 20M min Between main power supply terminals and chassis 500V DC 20M min Dielectric strength Between control power supply...

Page 29: ...to zero for ramp lower limit function Check the value of the parameter setting screen and position of the external adjuster VR to which the ramp lower limit is allocated Check VR position on monitor...

Page 30: ...30 MEMO...