3. Primary operation
Primary operation
3.9 The basic operation procedure for Combined mode 3 (
,
P.79=6)
●
The target frequency is determined by
communication
.
W
hen
RL, RM, RH
and REX are
‘
on
’
, the
target frequency is determined by
combination of multi-speed stage levels
(Please refer to
P.4~P.6, P.80~P.84, P.86, P.126~P.128).
When
EXJ
is
‘
on
’
, the target frequency is determined by
the set value of P.15. Acceleration/deceleration time is set by the value of P.16. The inverter
starting
is determined by
external terminals
. The functions of P.996, P.998 and P.999 can be
accomplished by
communication
.
3.10 The basic operation procedure for Combined mode 4 (
,
P.79=7)
●
The
target frequency
of the inverter is determined by the
external terminals
,
‘
external voltage
signal
’
,
‘
external current signal
’
or
‘
combination of multi-speed stage levels
’
terminals. The
inverter
starting
is determined by
communication
(including
‘
Reset
’
).
3.11 The basic operation procedure for Combined mode 5 (
,
P.79=8)
●
The target frequency is determined by
DU01 operation panel
. When
RL, RM, RH
and REX are
‘
on
’
, the target frequency is determined by
combination of multi-speed stage levels
(Please refer
to P.4~P.6, P.80~P.84, P.86, P.126~P.128). When
EXJ
is
‘
on
’
, the target frequency is determined
by the set value of P.15. Acceleration/deceleration time is set by the value of P.16. The inverter
starting
is determined by
external terminals
.
3.12 Operation
3.12.1 Check and preparation before operation
Before the start of operation shall examine the following several aspects:
1. Check the wiring is ture or not. Especially check ac motor driver output terminals (V, U, W)
cannot be connected to the power, confirm grounding terminals ground well.
2.
Confirm the terminal or the exposure of charged have short circuit or not.
3. Confirm terminal connections, plug connector (optional) and screw fastening are all fastening or
not.
4.
Confirm motor have not connect the mechanical device.
5. All switch must disconnected before power on. Ensure the inverter won't start and without
abnormal action when power on.
6. Turn on the power must after cover installation.
7. Wet hand prohibit operation switch.
8. Ensure the following several aspects after power on:
1). Keyboard panel should be shown no fault.
(1). If the keyboard panel is not chosen, the
indicating lamp of
POWER
is lit, and
indicating
lamp of
ALARM
is not lit
。
(2). If the keyboard panel is n chosen, the
indicating lamp of
and
are all lit
。
2). The cooling fan which installed inside inverter (the type which including the fan) must be