22
2.
Introduction of Shihlin Inverter
Introduction of Inverter
If
‘
Source Input
’
mode is selected, the function of the multi-function contro
l
; terminal is active when it
is shorted with PC or connected with the external PLC. In this mode, the current flows into the
corresponding terminal when it is
‘
on
’
. Terminal PC is common to the contact input signals. When using
an external power supply for transistor output, please use terminal SD as a common to prevent
misoperation caused by leakage current.
Source Input: the multi-function control terminal is
connected with open-emitter PLC and external power supply
PLC
I
STF
STR
PC
Inverter
DC
24V
SD
DC
24V
Main-circuit terminals
Terminal name
Remarks
R- S- T
Connect to the commercial power supply.
U-V-W
Connect to three-phase squirrel-cage motor.
P-P1
Connect to DC reactor
P- PR
Connect to braken resistors. (Note1, 2)
P- N
Connect to braken unit. (Note3)
The grounding terminal for the case of the inverter. For 220V series, the third type
of grounding shall be adopted. For 440V series, special type of grounding shall be
adopted. (Note4)