65
4. Parameter description
Parameter
Parameter
Factory setting
Setting range
Remarks
50Hz
When P.189=1
38
60Hz
1~400Hz
When P.189=0
0
The range for the input voltage signal
(terminal 2-5/4-5) is 0~5V.
73
0
0, 1
1
The range for the input voltage signal
(terminal 2-5/4-5) is 0~10V.
139
0.00%
0.00%~200.0%
---
140
100.0%
0.10%~200.0%
---
141
0
0~11
---
< Setting >
•
There are 2 digits in P.141, every digit have the different meaning, relevant positions as following:
•
Now let
’
s see some examples:
Example 1: This is the most used setting. When the inverter is in
‘
external mode
’
,
‘
combined mode
2
’
or
‘
combined mode 4
’
, and the frequency is set by terminal 2-5
。
Parameter setting
:
P.38 = 60.00Hz
,
P.73 = 1
,
P.139 = 0%
,
P.140 = 100%
,
P.141 = 0