3 Function parameter schedule graph
18
F7.02
VCI max. provision
0.00
-
10.00V
0.01V 9.90V
○
F7.03
VCI max. provision corresponding freq.
0.00
-
high limit frequency
0.01 Hz 50.00Hz
○
F7.04
~
F7.17
Reversed
F8–motor and vector control parameter group
Function
code
name
Set range
unit
Factory default
modifi
cation
F8.00 reserved
F8.01
Motor rated voltage
1
-
480V 1V
Depend on device type
×
F8.02
Motor rated current
0.1
-
999.9A
0.1A
Depend on device type
×
F8.03
Motor rated frequency
1.00
-
400.00Hz
0.01Hz Depend on device type
×
F8.04
Motor rated speed
1
-
9999r/min
1r/min
Depend on device type
×
F8.05
Motor pole
2-14
2
Depend on device type
×
F8.06
Motor rated power
0.1
-
999.9KW
0.1
Depend on device type
×
F8.07
reserved
F8.08
reserved
F8.09
reserved
F8.10
reserved
F8.11
reserved
F8.12
reserved
F8.13
reserved
F8.14
reserved
F8.15
reserved
F8.16
Frequency display offset
0.00Hz-2.00Hz 0.01Hz
0.20Hz
○
F8.17
reserved
F9 –protection correlative function parameter group
Function
code
name
Set range
unit
Factory
default
modifi
cation
F9.00
reserved
F9.01
Failure self-renew
times
0
-
10
0 shows no automatic reset function
Remark: no automatic reset function for
overload and overheating
1 0
×
F9.02
Failure self-renew interval
0.5
-
20.0S
0.1S 5.0S
×
F9.03
Motor overload
protection mode selection
0: no action
1: inverter close off output
1 1
×