www.enc.net.cn/en
Tel/Fax:86-755-26984485/26985120
2 Type and specification of the inverter
7
2.6
The inverter
interface specifications
Fig.2-4
(1) P1 terminal function description
item
symbol
name
Function description
Spec.
FWD
Forward run
command
run
command
REV
Reverse run
command
Forward reverse run command,
see F5.08 group double-wire and
three-wire control function
description
X1
Multi-function input 1
X2
Multi-function input 2
X3
Multi-function input 3
Used for multi-function input
terminal, for detailed see function
parameter F5 group input end
function description.
Input impedance: R=2K
Ω
Max. input frequency: 200Hz
VCC
+5V power supply
P5V power supply.
(negative pole: GND)
Max. output current: 50mA
Mul
ti-fu
nct
ion inpu
t ter
m
in
a
GND
+5V power supply
negative pole
Reference ground of analog
signal and +5V power supply
Analog value
input
VCI
Analog value input
VCI
Accept analog voltage input
Input voltage range:0~5V
(Input impedance:10 K
Ω
)
Resolution:1/1000
Summary of Contents for EDS780 Series