VACUUM LEAK DETECTOR VLR ..
2020-06-29
2
1. Object
Vacuum leak detector of the type VLR ..(dots stand for alarm vacuum) as part of a leak detec-
tion system in the following versions:
a) VLR ..
b) VLR .. /E (extended version, i.e. either a leak probe or solenoid valve or both can be con-
nected in addition)
Leak probe:
Either in place of the liquid stop valve if special installation conditions or
resistancy matters make it necessary or as a probe used separately (e.g.
in the leakage containment).
Solenoid valves:
Must be used
whenever tanks are operated at
more than 5 bar
overlay
pressure or if resistancy requirements make them necessary (system is
then executed resistant up to the solenoid valves).
2. Area of application
2.1. Interstitial space requirements
•
Vacuum resistance to the operating vacuum of the leak detector, also taking fluctuations in
temperature into account.
•
Assurance of the suitability of the interstitial space as part of a leak detection system (e.g.
DIN standards, proofs of usability issued by the building inspection authorities, determina-
tion of suitability etc.)
•
No leak detection liquid in the interstitial space (see App. A if this is nevertheless the case)
•
The pipes listed under section 2.4 meet the above requirements acc. to App.E.
•
The volume of the space monitored by the leak detector may not exceed 8 m
3
for tanks and
10 m
3
for pipes. The manufacturer recommends not exceeding 4 m
3
.
2.2. Material to be conveyed
Liquids hazardous to water with a flash point > 60°C (for Germany > 55°C acc. TRGS 509 and
751), where no potentially explosive vapour-air mixtures occur.
If different liquids are conveyed in individual pipes and monitored with one leak detector, these
liquids may not have a negative influence on one another nor lead to chemical reactions.
2.3. Resistance / materials
For the leak detector VLR .. the material polyamide (PA) in connection with brass (MS-58) or
(1.4301, 1.4306, 1.4541)
1
or 1.4571
2
, as well as the material of the connecting tubes used has
to be sufficiently resistant to the material to be stored/conveyed.
If the materials mentioned above are not sufficiently resistant, correspondingly resistant sole-
noid valves can be used in the tanks.
1
cf. DIN 6601, centre column
2
cf. DIN 6601, right-hand column
Summary of Contents for VLR 230
Page 19: ...I I II II III III IV IV 21 21 21 21 20 20 20 20 27 11 2002 P 060 000...
Page 27: ...21 02 2017 SL 853 600 2 6 4 5 3 11 12 1 AC DC 105 106 102 71 01 69 24 1 24 3 59 09 76 17 60 Rp...
Page 29: ...22 84 85 85 22 52 98 98 0 Kl 1 0 17 12 2002 P 115 392 21 21 20 20 90 90...
Page 39: ...28 06 2005 D i hrbild Abmes 200 3 0 0 2 6 0 220 T 140 8 Dimension Drilling...