APPENDIX E
VACUUM LEAK DETECTOR
VL(R) ..
01/02/2018
- E-1 -
E.1 H
max
Depending on density
In this appendix, VL .. stands for all versions, i.e. also for VLR .. or VLR ../E
Density of the
product stored
[kg/dm
3
]
H
max.
[m]
VL 230 VL 255 VL 330 VL 410 VL 500 VL 570
0.8
2.6
2.9
3.8
4.8
6.0
6.9
Aboveground tank(s)
and pipe(s)
0.9
2.3
2.6
3.4
4.3
5.3
6.1
1.0
2.0
2.3
3.1
3.9
4.8
5.5
Above- and under-
ground tank(s)
/ pipe(s)
1.1
1.9
2.1
2.8
3.5
4.4
5.0
1.2
1.7
1.9
2.6
3.2
4.0
4.6
1.3
1.6
1.8
2.4
3.0
3.7
4.2
1.4
1.5
1.6
2.2
2.8
3.4
3.9
1.5
1.4
1.5
2.0
2.6
3.2
3.7
1.6
1.3
1.4
1.9
2.4
3.0
3.4
1.7
1.2
1.4
1.8
2.3
2.8
3.2
1.8
1.1
1.3
1.7
2.2
2.7
3.1
1.9
1.1
1.2
1.6
2.0
2.5
2.9
E.2 Max. Tank height depending on density
Density of the
product stored
[kg/dm
3
]
H
max.
[m]
VL 34
VL 230 VL 255 VL 330 VL 410 VL 500 VL 570
0.8
7.5
17.3
19.1
23.4
23.8
24.5
24.2
Above-
ground tanks
0.9
6.6
15.3
17.0
20.8
21.1
21.8
21.5
1.0
6.0
13.8
15.3
18.7
19.0
19.6
19.4
Above- and
underground
tanks
1.1
5.4
12.6
13.9
17.0
17.3
17.8
17.6
1.2
5.0
11.5
12.8
15.6
15.8
16.4
16.2
1.3
4.6
10.6
11.8
14.4
14.6
15.1
14.9
1.4
4.3
9.9
10.9
13.4
13.6
14.0
13.8
1.5
4.0
9.2
10.2
12.5
12.7
13.1
12.9
1.6
3.7
8.6
9.6
11.7
11.9
12.3
12.1
1.7
3.5
8.1
9.0
11.0
11.2
11.5
11.4
1.8
3.3
7.7
8.5
10.4
10.6
10.9
10.8
1.9
3.1
7.3
8.1
9.8
10.0
10.3
10.2
Summary of Contents for VLR 230
Page 19: ...I I II II III III IV IV 21 21 21 21 20 20 20 20 27 11 2002 P 060 000...
Page 27: ...21 02 2017 SL 853 600 2 6 4 5 3 11 12 1 AC DC 105 106 102 71 01 69 24 1 24 3 59 09 76 17 60 Rp...
Page 29: ...22 84 85 85 22 52 98 98 0 Kl 1 0 17 12 2002 P 115 392 21 21 20 20 90 90...
Page 39: ...28 06 2005 D i hrbild Abmes 200 3 0 0 2 6 0 220 T 140 8 Dimension Drilling...