3.1.5 Information retrieval

The following table shows the signification of the operational data of the control system :

1st line on display

2nd line on display

(informational value)

Signification

up time

hours: X
(in hours)

Shows the cumulative operating times 

of the control system in hours. The 

value can be reset to 0 by pressing 
the keys 

.

total pump hours

P1  XXXX
(in hours)

Shows the cumulative runtimes of the 

pumps in hours. The value can be 

reset to 0 (separately for both pumps)
by pressing the keys 

.

pump starts

P1  XXXX
(in number)

Shows the number of pump starts. The 

value can be reset to 0 (separately 

for both pumps) by pressing the keys 

.

next maintenance

within days:XXXX
(in days)

Shows the number of days until the 

next maintenance. The information 

is saved at intervals of 4 hours. The 

initial value can be preset between 

365 and 0 days.

3.1.6 Warnings and notices of malfunction

The following warnings and notices of malfunction can be indicated on the display. In the fault 

protocol, the according data will be recorded :

2nd line on 

display

Signification

Alarm

Protocol 

signal

Fault load

Current flow below 0,5 A. Either 

no pump is connected, or a 

phase is lacking.

This malfunction can be suppressed, if for the 

motor current monitoring 0.0A are set in the menu 

“current limitation“.

If both pump currents are set 

to 0,0A, the control system is 

running in the test mode. The 

pumps are not deactivated. All 

functions of the control system 

are enabled. The motor current 

is not monitored.

Yes

Last

    

  

    

  

    

  

    

  

Summary of Contents for ZPS 1.3

Page 1: ...Electronic pump control Operation and assembly instructions CONTROL BOX ZPS 1 3 9001 3 11 19...

Page 2: ...English 3 Deutsch 17 Fran ais 32 Italiano 47 Nederlands 62 Espa ol 76 Portugu s 91...

Page 3: ...l characteristics pg 5 2 3 Technical data pg 5 3 OPERATION OF THE CONTROL SYSTEM pg 6 3 1 Operator control panel and operational elements pg 6 3 1 1 Key pg 6 3 1 2 Indications on the display pg 7 3 1...

Page 4: ...ce of at least 3 mm The connection must be used exclusively to provide the power to the product If the power cord is damaged to prevent possible danger it must be replaced by the manufacturer customer...

Page 5: ...istics Clear LCD display Hand Stop Auto Function 1 acknowledgement button 2 parameter select buttons Menu which can be switched through Internal acoustic alarm Programmable operation and collective fa...

Page 6: ...y pressing this key the preferred pump is switched on without delay No other function of the program is enabled The green LED of one pump flashes ATTENTION If the ATEX mode is enabled the pump can onl...

Page 7: ...re displayed alternately In case of failure the actual failure status is displayed see point 3 1 6 The red LEDs of the pump will be seen red flashing light Parameter setting In the upper line the desi...

Page 8: ...sensor Flooding alarm level Additionally this level is constantly evaluated on the input for the floating switch HW independent from the selected level transmitter Thereby if necessary 2 different HV...

Page 9: ...efly started if no request occurs by the switch on level within 24 hours If the ATEX mode is enabled the 24h starting is only taking place if the turn off level is exceeded acoustic alarm is activated...

Page 10: ...via external sensor intern converter matching calibration By pressing the key sequence the zero point of the internal converter is adjusted The adjustment has to be carried out while the pilot tube i...

Page 11: ...maintenance within days XXXX in days Shows the number of days until the next maintenance The information is saved at intervals of 4 hours The initial value can be preset between 365 and 0 days 3 1 6...

Page 12: ...anually Yes Pump TH1 TH2 Phase error A phase of the power supply has failed Yes Dreh Fault ATEX The ATEX mode is activated and the level is below the switch off point of the selected pump Yes Atex Run...

Page 13: ...rding to the connection diagram shown below Connection of a 3 phase Motor Connection of a single phase Motor with internal capacitor Mains connection Pump1 Protective conductors Mains connection Pump1...

Page 14: ...t board The active sensor can be selected in the menu level control and therm malfunction If the thermostatic switch TH2 is not necessary a bridge has to be inserted on this contact point The thermost...

Page 15: ...verter adjustment serves for the accurate adjustment of the zero point In order to equalise possible air leaks inside the pneumatic level measuring device the pilot tube has to be fully emerged from t...

Page 16: ...idge thermal contacts TH2 5 Disable thermic error for the pump If the respective level sensors are connected all program functions can be checked without having to connect the pump 4 DISPOSAL Only for...

Page 17: ...Contact Information SFA Australia Pty Ltd Unit 10 25 Gibbes Street Chatswood NSW 2067 Phone 1300 554 779 E GENERAL ENQUIRIES info saniflo com au E TECHNICAL SUPPORT technical saniflo com au...

Reviews: