SFA ZPS 1.3 Operation And Assembly Instructions Download Page 7

7

By pressing one of these two keys, the menu is switched to the next menu item in 

the indicated direction.
If the menu is enabled, (see key SELECTION 

), the set values can be modified 

via those keys (some modifications are only possible in the operating mode 

“Stop”). The more you press the key, the faster it scrolls.

(Selection/

 Stop)

By pressing this key, the set values in the active menu are enabled.  The activated 
text is starting to flash (modification mode) and can be modified by using 

.

By repeatedly pressing these keys, the set value becomes permanent (flashing 

stops), which means that it will be saved even if the control system is turned off.

3.1.2 Indications on the display

Normal operation :

During operation of the control system, the upper line of the LCD display indicates the actual liquid 

level or the switching status of the floating switch. In the lower line of the display, information about 

the actual operational status of the control system of the pump will appear. When the pump is 

running, the motor current and the operating condition are displayed alternately. In case of failure, 

the actual failure status is displayed (see point 3.1.6). The red LEDs of the pump will be seen red 

flashing light.

Parameter setting :

In the upper line, the designation of the parameter is displayed; the lower line displays the current 
value of the parameter. The values can be modified by using the keys 

 and 

 as described 

in 3.1.1.

Information retrieval :

Information values such as maintenance intervals, operating hours, pump starts and error list can 

be displayed and modified in the same way as the control parameters. The error list can save up 

to 32 records respectively. The recording is carried out by means of a shift register, which means 

that the earliest error is deleted automatically.

3.1.3 Normal operation

During normal operation, the three operating modes are indicated on the display as follows.

Pressed key

2nd line on display

Signification

Hand 1       P1   4,7A

The pump P1 has been switched on manually.

Stop 1         P1  0,0 A

The pump motor is switched off. The level evaluation, 

including the flood control, remains enabled. 

The pump motor is not activated during 

flooding alarm.

Auto 1         P1  4,7A

The pump is switches on or off, according to the level 

requirement. Here, pump P1 is active at the moment.

WARNING

Summary of Contents for ZPS 1.3

Page 1: ...Electronic pump control Operation and assembly instructions CONTROL BOX ZPS 1 3 9001 3 11 19...

Page 2: ...English 3 Deutsch 17 Fran ais 32 Italiano 47 Nederlands 62 Espa ol 76 Portugu s 91...

Page 3: ...l characteristics pg 5 2 3 Technical data pg 5 3 OPERATION OF THE CONTROL SYSTEM pg 6 3 1 Operator control panel and operational elements pg 6 3 1 1 Key pg 6 3 1 2 Indications on the display pg 7 3 1...

Page 4: ...ce of at least 3 mm The connection must be used exclusively to provide the power to the product If the power cord is damaged to prevent possible danger it must be replaced by the manufacturer customer...

Page 5: ...istics Clear LCD display Hand Stop Auto Function 1 acknowledgement button 2 parameter select buttons Menu which can be switched through Internal acoustic alarm Programmable operation and collective fa...

Page 6: ...y pressing this key the preferred pump is switched on without delay No other function of the program is enabled The green LED of one pump flashes ATTENTION If the ATEX mode is enabled the pump can onl...

Page 7: ...re displayed alternately In case of failure the actual failure status is displayed see point 3 1 6 The red LEDs of the pump will be seen red flashing light Parameter setting In the upper line the desi...

Page 8: ...sensor Flooding alarm level Additionally this level is constantly evaluated on the input for the floating switch HW independent from the selected level transmitter Thereby if necessary 2 different HV...

Page 9: ...efly started if no request occurs by the switch on level within 24 hours If the ATEX mode is enabled the 24h starting is only taking place if the turn off level is exceeded acoustic alarm is activated...

Page 10: ...via external sensor intern converter matching calibration By pressing the key sequence the zero point of the internal converter is adjusted The adjustment has to be carried out while the pilot tube i...

Page 11: ...maintenance within days XXXX in days Shows the number of days until the next maintenance The information is saved at intervals of 4 hours The initial value can be preset between 365 and 0 days 3 1 6...

Page 12: ...anually Yes Pump TH1 TH2 Phase error A phase of the power supply has failed Yes Dreh Fault ATEX The ATEX mode is activated and the level is below the switch off point of the selected pump Yes Atex Run...

Page 13: ...rding to the connection diagram shown below Connection of a 3 phase Motor Connection of a single phase Motor with internal capacitor Mains connection Pump1 Protective conductors Mains connection Pump1...

Page 14: ...t board The active sensor can be selected in the menu level control and therm malfunction If the thermostatic switch TH2 is not necessary a bridge has to be inserted on this contact point The thermost...

Page 15: ...verter adjustment serves for the accurate adjustment of the zero point In order to equalise possible air leaks inside the pneumatic level measuring device the pilot tube has to be fully emerged from t...

Page 16: ...idge thermal contacts TH2 5 Disable thermic error for the pump If the respective level sensors are connected all program functions can be checked without having to connect the pump 4 DISPOSAL Only for...

Page 17: ...Contact Information SFA Australia Pty Ltd Unit 10 25 Gibbes Street Chatswood NSW 2067 Phone 1300 554 779 E GENERAL ENQUIRIES info saniflo com au E TECHNICAL SUPPORT technical saniflo com au...

Reviews: