Signification

Alarm

Protocol 

signal

Fault pump 1

The motor current monitoring system has detected 

an exceedance of the set limit value and has shut 

down the pump motor.

Yes

IP1

Fault high water

The HW-sensor reports an alarm and switches on 

the pump. The HW-malfunction acknowledges itself 

when the turn-on level is reached.

Yes

HW

Fault I<3mA

The external sensor is selected, but the current 

is <3mA. There might be a disconnection, or 

the sensor might be defective. The malfunction 

acknowledges itself when the sensor current is 

within the normal range.

Yes

I<3mA

Fault SW

The floating switches are connecting in the wrong 

sequence (e.g. the lower floating switch is open 

when the upper floating switch closes). 

Yes

SW

Pump
Fault TH1
Fault TH2

Activation of the thermal control of the pump 

motor. The malfunction TH1 acknowledges itself 

after the motor has cooled down; TH2 has to be 

acknowledged manually.

Yes

Pump

TH1
TH2

Phase error

A phase of the power supply has failed.

Yes

Dreh

Fault ATEX

The ATEX mode is activated and the level is below 

the switch-off point of the selected pump.

Yes

Atex

Run-time alarm

The runtime monitoring of the pump has been 

exceeded 3 times in succession.

Yes

Time

3.2 Assembly and electrical connections

All electrical connections are to be established by an authorised 

professional only. Settings and adjustments on the control system 

as well as the commissioning of the control system are to be 

carried out by qualified persons only.

3.2.1 Mechanical fixation

The control system has to be fixed on an even surface. In order to fasten the control system, the 

housing cover has to be opened.

3.2.2 Mains connection

The left cable gland is intended for the cable entry of the mains cable. The separate cables are 

to be clamped into the spring terminals in the manner described below. According to the motor 

which is used, a single-phase or a three-phase connection can be established.

The power supply has to be secured by an independent all-pole 

fuse which can be switched off (max. 20 A).

    

  

    

  

    

  

    

  

    

  

    

  

Summary of Contents for ZPS 1.3

Page 1: ...Electronic pump control Operation and assembly instructions CONTROL BOX ZPS 1 3 9001 3 11 19...

Page 2: ...English 3 Deutsch 17 Fran ais 32 Italiano 47 Nederlands 62 Espa ol 76 Portugu s 91...

Page 3: ...l characteristics pg 5 2 3 Technical data pg 5 3 OPERATION OF THE CONTROL SYSTEM pg 6 3 1 Operator control panel and operational elements pg 6 3 1 1 Key pg 6 3 1 2 Indications on the display pg 7 3 1...

Page 4: ...ce of at least 3 mm The connection must be used exclusively to provide the power to the product If the power cord is damaged to prevent possible danger it must be replaced by the manufacturer customer...

Page 5: ...istics Clear LCD display Hand Stop Auto Function 1 acknowledgement button 2 parameter select buttons Menu which can be switched through Internal acoustic alarm Programmable operation and collective fa...

Page 6: ...y pressing this key the preferred pump is switched on without delay No other function of the program is enabled The green LED of one pump flashes ATTENTION If the ATEX mode is enabled the pump can onl...

Page 7: ...re displayed alternately In case of failure the actual failure status is displayed see point 3 1 6 The red LEDs of the pump will be seen red flashing light Parameter setting In the upper line the desi...

Page 8: ...sensor Flooding alarm level Additionally this level is constantly evaluated on the input for the floating switch HW independent from the selected level transmitter Thereby if necessary 2 different HV...

Page 9: ...efly started if no request occurs by the switch on level within 24 hours If the ATEX mode is enabled the 24h starting is only taking place if the turn off level is exceeded acoustic alarm is activated...

Page 10: ...via external sensor intern converter matching calibration By pressing the key sequence the zero point of the internal converter is adjusted The adjustment has to be carried out while the pilot tube i...

Page 11: ...maintenance within days XXXX in days Shows the number of days until the next maintenance The information is saved at intervals of 4 hours The initial value can be preset between 365 and 0 days 3 1 6...

Page 12: ...anually Yes Pump TH1 TH2 Phase error A phase of the power supply has failed Yes Dreh Fault ATEX The ATEX mode is activated and the level is below the switch off point of the selected pump Yes Atex Run...

Page 13: ...rding to the connection diagram shown below Connection of a 3 phase Motor Connection of a single phase Motor with internal capacitor Mains connection Pump1 Protective conductors Mains connection Pump1...

Page 14: ...t board The active sensor can be selected in the menu level control and therm malfunction If the thermostatic switch TH2 is not necessary a bridge has to be inserted on this contact point The thermost...

Page 15: ...verter adjustment serves for the accurate adjustment of the zero point In order to equalise possible air leaks inside the pneumatic level measuring device the pilot tube has to be fully emerged from t...

Page 16: ...idge thermal contacts TH2 5 Disable thermic error for the pump If the respective level sensors are connected all program functions can be checked without having to connect the pump 4 DISPOSAL Only for...

Page 17: ...Contact Information SFA Australia Pty Ltd Unit 10 25 Gibbes Street Chatswood NSW 2067 Phone 1300 554 779 E GENERAL ENQUIRIES info saniflo com au E TECHNICAL SUPPORT technical saniflo com au...

Reviews: